Instruction manual

7. Programming Features
157
Building Interface Circuits with External Devices
Using Input Signals
The functions of multi-function input terminals S1 to S7 can be changed
as necessary by setting constants n050 to n056. With the exception of
the value “28,” the same value cannot be set for more than one of these
constants.
The function of terminal S1 is set in constant n50. Likewise, the func-
tions of terminals S2 to S7 are set in constants n51 to n56. The follow-
ing functions can be set.
Setting Name Description Ref.
0 FWD/REV RUN command
(3-wire sequence selection)
Setting possible only for
n052.
159
1 FORWARD RUN command
(2-wire sequence selection)
137
2 REVERSE RUN command
(2-wire sequence selection)
137
3 External fault
(NO contact input)
Inverter stops for an external
fault signal input. Digital
Operator displays EF. *
-
4 External fault
(NC contact input)
-
5 Fault reset Resets a fault. Fault reset
not effective when the RUN
signal is ON.
-
6 Multi-step speed reference 1 139
7 Multi-step speed reference 2 139
8 Multi-step speed reference 3 139
9 Multi-step speed reference 4 139
10 JOG command 141
11 Acceleration/deceleration
time selection 1
143
12 External baseblock,
NO contact input
Motor coasts to a stop for
this signal input. Digital
Operator displays .
-
13 External baseblock,
NC contact input
-
* Numbers 1 to 7 are displayed for to indicate the terminal numbers S1 to
S7.