Typical Settings
• To operate the Inverter with a frequency reference of 0% to 100%
at an input voltage of 0 to 5 V
• To operate the Inverter with a frequency reference of 50% to
100% at an input voltage of 0 to 10 V
Adjusitng Frequency Upper and Lower Limits
• Frequency Reference Upper Limit (n033)
Sets the upper limit of the frequency refer-
ence in units of 1%.
(n011: Max. Output Frequency = 100%)
Factory setting: 100%
• Frequency Reference Lower Limit (n034)
Sets the lower limit of the frequency reference in units of 1%.
(n011: Max. Output Frequency = 100%)
When operating at a frequency reference of 0, operation is continued
at the frequency reference lower limit.
However, if the frequency reference lower limit is set to less than the
Minimum Output Frequency (n016), operation is not performed.
Factory setting: 0%
Max. frequency (100%)
Gain n068 = 200
Bias n069 = 0
Max. frequency (100%)
Gain n068 = 100
Bias n069 = 50
0 V 10 V
Internal
frequency
reference
Frequency
Upper Limit
(n033)
Frequency
Lower LiMIT
(n034)
Set frequency reference