Instruction manual

7. Programming Features
141
Operating at Low Speed
By inputting a JOG command and then a FORWARD (REVERSE)
RUN command, operation is enabled at the jog frequency set in n032.
When multi-step speed references 1, 2, 3 or 4 are input simultaneously
with the JOG command, the JOG command has priority.
Note: Input terminals S1 to S7 can be used only from DeviceNet communica-
tions. There are no corresponding external input terminals.
Adjusting Speed Setting Signal
The relationship between the analog inputs and the frequency reference
can be set to provide the frequency reference as analog inputs to Digital
Operator terminals CN2-1, CN2-2, and CN2-3.
1. Analog Frequency Reference Gain (n068 for voltage input, n071 for
current input)
The frequency reference provided when the analog input is 10 V (or
20 mA) can be set in units of 1%. (Max. Output Frequency
n011=100%)
* Factory setting: 100%
2. Analog Frequency Reference Bias (n069 for voltage input, n072 for
current input)
The frequency reference provided when the analog input is 0 V
(4 mA or 0 mA) can be set in units of 1%. (Max. Output Frequency
n011=100%)
* Factory setting: 0%
Constant No. Name Setting
n032 Jog Frequency Factory setting: 180 r/min
n050 to n056 Jog References Set to 10 for any constant.
( ) indicates the value when a current
reference input is selected.
Frequency Reference