Instruction manual

112
01 04 NetRef Sets the Frequen-
cy Reference right.
(See note 1.)
00: Use the Fre-
quency Reference
input method set in
constant n004
(Frequency Refer-
ence Selection).
01: Enables the
Frequency Refer-
ence from De-
viceNet (bytes 2
and 3).
00,01 00 OK OK Byte
06 Drive
Mode
Sets the Inverter's
control mode. (See
note 3.)
00: Vector control
01: V/f control
00 to
03
01 OK OK Byte
07 Speed
Actual
Indicates the
Inverter’s speed.
(See note 2.)
Minimum units: r/
min/2
SS
SS
: Speed scale
(attribute 16)
--- 0000 OK --- Word
08 Speed
Ref
Sets or references
the Inverter’s
speed reference.
(See note 2.)
Minimum units: r/
min/2
SS
SS
: Speed scale
(attribute 16)
0 to
max.
fre-
quen-
cy
0000 OK OK Word
09 Current
Actual
Indicates the
Inverter’s output
current.
Minimum units:
0.1 A/2
CS
CS
: Current scale
(attribute 17)
--- 0000 OK --- Word
0F Power
Actual
Indicates the
Inverter’s output
power.
Minimum units: W/
2
PS
PS
: Power scale
(attribute 1A)
--- 0000 OK --- Word
In-
stance
At-
tribute
Name Contents Setting
Range
Factory Set-
ting (Hex)
Read Write Size