Instruction manual
104
• Object Contents
* 1. The factory setting of the motor rated current depends on the Inverter’s
capacity.
* 2. The table shows the setting range and factory setting for a 200 V Class
Inverter. Double these values when using a 400 V Class Inverter.
Control Supervisor Object (Class 29 Hex)
The Control Supervisor object is the object that manages information
and functions related to the Inverter’s control I/O. Basic control I/O
functions are assigned to this object, such as the Inverter’s Run, Stop,
and Fault Detect controls.
The Control Supervisor object’s functions are shared with the I/O mes-
sage communications functions. When an I/O message communications
connection is established, the values set with this object will be over-
written by the values set by I/O messages.
• Supported Services
In-
stance
At-
tribute
Name Contents Setting
Range
Factory Set-
ting (Hex)
Read Write Size
00 01 Object
Soft-
ware
Revision
Indicates the Mo-
tor Data object's
software revision.
--- 0001 OK --- Word
01 03 Motor
Type
Indicates the type
of motor being
used.
7: Squirrel-cage
induction motor
--- 07 OK --- Byte
06 Rated
Current
This attribute can
be used to set/ref-
erence the mo-
tor’s rated current.
Setting units:
0.1 A
0 to
150%
of the
Invert-
er’s
rated
current
See note
1.
OK OK Word
07 Rated
Voltage
This attribute can
be used to set/ref-
erence the mo-
tor’s rated voltage.
Setting units: 1 V
0 to
255 V
See
note 2.
00C8
See note
2.
OK OK Word
Service
Code
(Hex)
Service Name Description
0E Get_Attribute_
Single
Returns the contents of the specified
attribute.