Instruction manual
6. Operating with DeviceNet Communications
103
Motor Data Object (Class 28 Hex)
The Motor Data object is the object that manages information and func-
tions related to the motor connected to the Inverter. The motor’s rated
current and rated voltage can be set or referenced with this object.
• Supported Services
02 0C Watch-
dog tim-
eout
action
Indicates the ac-
tion to take when a
timeout occurred
during internal pro-
cessing related to
communications.
00: Maintain until
reset or discon-
nected.
01: Disconnect au-
tomatically.
02: Perform the
operation again
while connected.
--- 00 OK --- Byte
0D Pro-
duced
connec-
tion path
length
Indicates the
transmission con-
nection path’s
number of bytes.
--- 0003 OK --- Word
0E Pro-
duced
connec-
tion path
Indicates the appli-
cation object that
transmits data
from the instance.
--- 62,34,37 OK --- Array
0F Con-
sumed
connec-
tion path
length
Indicates the re-
ception connection
path’s number of
bytes.
--- 0003 OK --- Word
10 Con-
sumed
connec-
tion path
Indicates the appli-
cation object that
receives data from
the instance.
--- 62,31,35 OK --- Array
Service
Code
(Hex)
Service Name Description
0E Get_Attribute_
Single
Returns the contents of the specified
attribute.
10 Set_Attribute_
Single
Changes the contents of the speci-
fied attribute.
In-
stance
At-
tribute
Name Contents Setting
Range
Factory Set-
ting (Hex)
Read Write Size