Operator`s manual
2.7 Arc Welding Instruction
2-238
2. Current command value /I Variable number /LI Variable number /I [Array
number] /LI [Array number]
Choose one of the tags from the following table.
(1) AWELD 6.0
The command value of the welding current is set to 6.0V.
(2) SET I000 500
AWELD I000
Set to 5.0V to which the command value of the welding current is set with I000.
No Tag Explanation Note
5
Current command
value
Specifies the command value of the welding cur-
rent.
This is a command value of the current which is
transmitted from the controller to the welder to
output the welding current from the welder. The
relation between the command welding current
and the output value is different depending on
the model of the welder.
Command value:
-14.00 V to +14.00 V
Variable I/LI/I[]/LI[]
can be used.
(Units: 0.01 V)
6
I Variable num-
ber/
LI Variable num-
ber/
I [Array number]/
LI [Array number]
Specifies the integer type variable number by
which the command value of the welding current
is set.
For details of the output characteristics of the welder, refer to the “Operator’s Manual for
Arc Welding”.
SUPPLE-
MENT
Example