Specifications

13
Standard Specifications
Item Specifications
Control Characteristics
Control Method
V/f Control, V/f Control with PG, Open Loop Vector Control, Closed Loop Vector Control, Open Loop Vector for PM, Closed Loop Vector for PM, Advanced Open Loop Vector for PM
Frequency Control Range
0.01 to 400 Hz
Frequency Accuracy
(Temperature Fluctuation)
Digital reference: within ±0.01% of the max. output frequency (−10 to +40°C)
Analog reference: within ±0.1% of the max. output frequency (25°C ±10°C)
Frequency Setting Resolution
Digital referece: 0.01 Hz
Analog referece: 0.03 Hz / 60 Hz (11 bit)
Output Frequency Resolution
0.001 Hz
Frequency Setting Signal
-10 to +10 V, 0 to +10 V, 4 to 20 mA, Pulse Train
Starting Torque
150%/3 Hz (V/f Control and V/f Control with PG), 200%/0.3 Hz*
1
(Open Loop Vector Control), 200%/0 r/min
*1
(Closed Loop Vector Control, Closed Loop Vector Control for PM,
and Advanced Open Loop Vector Control for PM), 100%/5% speed (Open Loop Vector Control for PM)
Speed Control Range
1:1500 (Closed Loop Vector Control and Closed Loop Vector for PM) 1:200 (Open Loop Vector Control) 1:40 (V/f Control and V/f Control with PG) 1:20 (Open Loop Vector for PM)
1:100 (Advanced Open Loop Vector for PM)
Speed Control Accuracy
±0.2% in Open Loop Vector Control (25°C ±10°C)
*2
, 0.02% in Closed Loop Vector Control (25°C±10°C)
Speed Response
10 Hz in Open Loop Vector (25°C ±10°C), 50 Hz in Closed Loop Vector Control (25°C±10°C) (excludes temperature
uctuation when performing Rotational Auto-Tuning)
Torque Limit
All Vector Control allows separate settings in four quadrants
Accel/Decel Time
0.00 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)
Braking Torque
Drives of 200/400 V 30 kW or less have a built-in braking transistor.
1. Short-time decel torque
*3
:
over 100% for 0.4/ 0.75 kW motors, over 50% for 1.5 kW motors, and over 20% for 2.2 kW and above motors
(over excitation braking/High-Slip Braking: approx. 40%)
2. Continuous regen. torque: approx. 20% (approx. 125% with dynamic braking resistor option
*4
: 10% ED,10s, internal braking transistor)
V/f Characteristics
User-selected programs and V/f preset patterns possible
Main Control Functions
Torque control, Droop control, Speed/torque control switching, Feedforward control, Zero-servo control, Momentary power loss ride-thru, Speed search, Overtorque detection, Torque limit,
17-step speed (max), Accel/decel time switch, S-curve accel/decel, 3-wire sequence, Auto-tuning (rotational, stationary), Online tuning, Dwell, Cooling fan on/off switch, Slip compensation,
Torque compensation, Frequency jump, Upper/lower limits for frequency reference, DC injection braking at start and stop, Overexcitation braking, High slip braking, PID control (with sleep
function), Energy saving control, MEMOBUS comm. (RS-485/422 max, 115.2 kbps), Fault restart, Application presets, DriveWorksEZ (customized function), Removable terminal block with
parameter backup function...
Protection Function
Motor Protection
Motor overheat protection based on output current
Momentary Overcurrent Protection Drive stops when output current exceeds 200% of Heavy Duty Rating
Momentary Overcurrent Protection Drive stops when output current exceeds 200% of Heavy Duty Rating
Momentary Overcurrent Protection Drive stops when output current exceeds 200% of Heavy Duty Rating
Overload Protection
Drive stops after 60 s at 150% of rated output current (Heavy Duty Rating)
*5
Overvoltage Protection
200 V class: Stops when DC bus exceeds approx. 410 V, 400 V class: Stops when DC bus exceeds approx. 820 V
Undervoltage Protection
200 V class: Stops when DC bus exceeds approx. 190 V, 400 V class: Stops when DC bus exceeds approx. 380 V
Momentary Power Loss Ride-Thru Immediately stop after 15 ms or longer power loss. Continuous operation during power loss of less than 2 s (standard)
Momentary Power Loss Ride-Thru Immediately stop after 15 ms or longer power loss. Continuous operation during power loss of less than 2 s (standard)
Momentary Power Loss Ride-Thru Immediately stop after 15 ms or longer power loss. Continuous operation during power loss of less than 2 s (standard)
*6
Heatsink Overheat Protection
Thermistor
Braking Resistance Overheat Protection Overheat sensor for braking resistor (optional ERF-type, 3% ED)
Braking Resistance Overheat Protection Overheat sensor for braking resistor (optional ERF-type, 3% ED)
Braking Resistance Overheat Protection Overheat sensor for braking resistor (optional ERF-type, 3% ED)
Stall Prevention
Stall prevention during acceleration/deceleration and constant speed operation
Ground Protection
Protection by electronic circuit
*7
Charge LED
Charge LED remains lit until DC bus has fallen below approx. 50 V
Operating Environment
Area of Use
Indoors
Ambient Temperature
−10 to +50°C (open chassis), −10 to +40°C (NEMA Type 1)
Humidity
95% RH or less (no condensation)
Storage Temperature
−20 to +60°C (short-term temperature during transportation)
Altitude
Up to 1000 meters (output derating of 1% per 100 m above 1000 m, max. 3000 m)
Shock
10 to 20 Hz: 9.8m/s²; 20 to 55 Hz: 5.9 m/s² for 200 V up to 45 kW and 400 V up to 75 kW, 2.0 m/s² for 200 V, 55 to 110 kW and 400 V, 90 to 315 kW
Safety Standard
EN954-1 safe category 3 stop category 0; EN ISO 13849-1; IEC EN 61508 SiL2
Protection Design
IP00 open-chassis, IP20, NEMA Type 1 enclosure
*1: Requires a drive with recommended capacity.
*2: Speed control accuracy may vary slightly depending on installation conditions or motor used. Contact Yaskawa for details.
*3: Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from the load) from the rated motor speed down to zero in the shortest time.
*4: If L3-04 is enabled when using a braking resistor or braking resistor unit, the motor may not stop within the specified deceleration time.
*5: Overload protection may be triggered at lower levels if output frequency is below 6 Hz.
*6:
Varies in accordance with drive capacity and load. Drives with a capacity of smaller than 11 kW in the 200 V (model: CIMR-AC2A0056) or 400 V (model: CIMR-AC4A0031) require a separate Momentary Power Loss Recovery Unit to continue operating
during a momentary power loss of 2 s or longer.
*7:
Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground fault is present at the output.