Specifications
1.3 Control and Indicators
1.3.1 Switch Controls
•
Alarm Acknowledge
•
Trouble Acknowledge
•
Signal Silence
•
System Reset/Lamp test
•
Programming buttons
–
Menu/Back
–
Back Space/Edit
–
OK
•
12 button keypad
1.3.2 LED Indicators
•
AC Power On (green)
•
Alarm (red)
•
Supervisory (yellow)
•
System Trouble (yellow)
•
Power Fault (yellow)
1.3.3 Audible Sounder
An Alarm/Trouble sounder is located on the Basic System Module (BSM)
1.4 Optional Modules
The following optional modules and features are available:
1.4.1 Digital Communicator (DACT)
The Model 7100-D provides an integral digital communicator (DACT), fully programmable from the keypad,
which is compatible with Digital Alarm Receivers (DACRs) that can receive the following formats:
SIA DC8
SIA DCS20
Ademco Contact ID
3+1 1400 Hz
3+1 2300 Hz
4+2 1400 Hz
4+2 2300 Hz
1.4.2 Class A Option Module (CAOM)
All 7100 Models are supplied with Class B Notification Appliance Circuits and Class B Signaling Line Circuits.
For Class A operation, the addition of a CAOM Module is required. This module operates with all 7100 Models
and enables the signaling line circuits to operate as Class A, Style 6 or 7 and notification appliance circuits to
operate as Class A, Style Z. It supplies the additional terminals for these circuits.
1.4.3 Municipal Circuit Option Module (MCOM)
The MCOM Module can trip a Local Energy City Master Box, operate in reverse polarity mode for leased line
connection, or energize a solenoid for releasing service.
10 of 46 9000-0447
•
Ground Fault (yellow)
•
NAC 1Silenced (yellow)
•
NAC 2 Silenced (yellow)
•
System Silenced (yellow)