CHAPTER2 DeviceNet Unit
Dedicated
command
BUSY
END
30ms or less 1ms or less 1ms or less1ms or less
Dedicated command
execution completion
Even after dedicated command
execution is completed, the END
signal does not turn ON until the
dedicated command input turns
OFF.
(3) When running a command was impossible from the start
(In the following cases, END will not turn ON, when running of command was
impossible from the start.)
•When a movement command (ABS-PT, INC-PT) was run without first completing
return to origin.
•When an operation start command (AUTO-R, STEP-R) was run without first com-
pleting return to origin (except when pre-operation selection parameter (single-
axis controllers : PRM48, dual-axis controllers : PRM9) was set to 1 or 3).
•When an unregistered point No. was specified, and a movement command (ABS-
PT, INC-PT) was run.
•When a dedicated command was run while in emergency stop or an interlock trig-
gered. (except for RESET and SERVO commands)
Dedicated
command
BUSY
END
30ms or less 1ms or less 30ms or less
(1) At the rise of the dedicated command input, the END signal turns off and the
BUSY signal turns on.
(2) Turns off (contact open) the custom dedicated input after the BUSY signal
turns on.
(3) Wait until the BUSY signal turns off. (The BUSY signal immediately turns off
since the command cannot be executed.)
(4) The END signal remains off when the BUSY signal turns off, indicating that
the command could not end normally.