PVH58 VENTING HARD PIPE OR FLEX
The PVH-58 Power Vent is approved for the following models only:
MQRB4436, MQRB5143, MQRB6961
Refer to fireplace manual (51MQ-MAN or 51MQ-MAN-II) for proper installation of your fireplace.
Approved For 5/8” Hard Pipe
The PVH-58 Power Vent is approved for use with Simpson Dura-vent Direct Vent system (Model DV-GS Series), and
AmeriVent Direct Vent Pipe System, ICC Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp.
Follow
installation instructions provided by the appropriate manufacturer for installation of pipe, and adhere to the clearance to
combustibles provided in this manual. Apply a bead of Mill Pac high temp sealant to all joints of pipes, adapters and
termination as recommended.
ADAPTERS REQUIRED FOR HARD PIPE INSTALLATION
FIREPLACE
MQRB4436
(5/7” Venting)
MQRB5143
(5/7” Venting)
MQRB6961
(7/10” Venting)
ADAPTERS REQUIRED
AT FIREPLACE
Z57DFA
Hard Pipe Adapter
Z57DFA
Hard Pipe Adapter
Pipe Reducer 10”Lg – 8”Sm
Pipe Reducer 7”Lg – 5”Sm
(Z69DFA- Kit)
ADAPTERS REQUIRED
AT POWER VENT
NONE NONE NONE
Approved For 5/7” And 7/10” Kingsman Flex (Z-Flex) Pipe
ADAPTERS REQUIRED FOR FLEX PIPE INSTALLATION
FIREPLACE
MQRB4436
(5/7” Venting)
MQRB5143
(5/7” Venting)
MQRB6961
(7/10” Venting)
ADAPTERS REQUIRED
AT FIREPLACE
NONE NONE NONE
ADAPTERS REQUIRED
AT POWER VENT*
Pipe Reducer 8”Sm – 7”Sm
ZDV5FC
(Z57PVA-Kit)
Pipe Reducer 8”Sm – 7”Sm
ZDV5FC
(Z57PVA-Kit)
Pipe Reducer 10”Sm– 8”Sm
Pipe Reducer 7”Sm – 5”Sm
(Z69PVA-Kit)
* One 12” section of hard pipe must be connected directly to the Power Vent before any adapters are connected.
Flex pipe is shipped in an unexpanded length. Therefore, when installing the pipe, expand it completely and then cut off
the remaining length. A flex pipe can be expanded to twice their shipped length (e.g. 4ft. to 8ft).
Place the spring spacers provided approximately every two feet to stabilize inner flex in the center of the outer flex pipe.
When forming bends place spring in bend or before and after.
ONLY VENTING COMPONENTS SPECIFICALLY APPROVED AND LABELED FOR YOUR FIREPLACE MAY BE USED.
WARNING: DO NOT mix parts from different systems unless stated in the manual.
92