MQRB5143 -See Thru Framing
An MQRB5143SK Kit is required for a See Thru Installation.
Before you begin Framing- Determine for both sides whether the Wall Surface will be flush with the face of the fireplace
(Fireplace and wall to be covered with Non-Combustibles, such as tile), or the Framing will
be flush with the face of the fireplace (Flat Wall appearance).
Note: If using Optional Surround, Maximum Thickness for Non-Combustible Material is 3/4”.
(Continued)
*15-3/8” Dimension is for Wall Surface Flush with Unit on Both Sides.
A
dd 1/2” to this Dimension for each side where a non-combustible wall
surface will cover the unit (See Nailing Tab Guide Page Also).
15-3/8”*
Framing Style shown is for illustration purposes only.
This structure is NOT load bearing.
[
Steel Stud Framin
g
Shown
]
Airbox must maintain Min. 1” Clearance
From Combustible [Wood] Framing.
Wood Framin
g
Stud -Rotated
Wood Framing Stud Rotated for Vent Clearance
22