User guide

33
Dissolved Oxygen Transmitter
GB Oxix Manual 080915
FW: 841013-009, 846001-002, 841513-009
Wiring Schematic #1
for " Magflux
®
with Blind Lid and Oxix
®
with Display Unit" from the opposite
page (page 32).
Oxix
®
with Display Unit
2-wire, shielded twisted cable
1. Connect lead "1" to slot "Display A"
2. Connect lead "2" to slot "Display B"
3. Connect the twisted shield to slot
"Display -"
Magflux
®
with Blind Lid
2-wire, shielded twisted cable
1. Connect lead "1" to slot "Display A"
2. Connect lead "2" to slot "Display B"
3. Connect the twisted shield to slot
"Display -"
1 2 3 4 5 6 7 8 9
Mains
supply
-mA- -D02--D01--DI--Display-
+ +A B C2 N02C NO N01 PE N L
- -
C1
Line
2 wire
shielded cable.
4 wire
shielded cable.
display unit
display unit
Display unitConverter #4Converter #1
Max. four MJK converters with Modbus
can be connected to one display unit:
521274
2,5
Main supply
Supply Fuse
10-30 V DC 1 A T
24 V AC 500 mA T
115 V AC 125 mA T
230 V AC 63 mA T
Sensor supply
Fuse 200 mA T
+DCGND A B
Red
Black
White
Green
Shield
521275
1
2
Shield
1
2
Shield