User guide
•Takecarenottodamagetheshieldcrosssectionwhenconnectingittothecontinuinglines.
This raises the RF resistance of the shield and radiates rather than discharges the RF energy
traveling on the shield. Shields, particularly those on control cables, must not be routed through
pin contacts (plug connectors).
•Whenshieldedcablesmustpassthroughaplugconnection,usethemetallichandguardofthe
plug for the continuation of the shield. It is strongly recommended that the shield be
uninterrupted whenever possible.
•Whenselectingshieldedcableforuseasmotorleads,itisimportanttoselectacablewhichis
designed for operation at the frequencies and power levels involved. Improper selection of
motor cable can cause high potential to exist on the shield. This could cause damage to the
inverter and other equipment and could pose a safety hazard.
•Separatepowerandcontrolwiring.NeverruntransducerorRS485wireinsameconduitasthe
power wiring.
•Usemetalconduitthatisgrounded.
•Keepperipheraldevicesandmachinesasfarfromthegroundcablesaspossible.Where
possible, use separate ground on the AQUAVAR.
•DonotuseenclosureofAQUAVAR as ground. The enclosure itself should be grounded.
•Useshielded(armoredVFD)cableforpowercables.(i.e.:Beldenwireandcable,Olflexcable.)
Appendix C
78