Help Windows
Window text Help Text
Regulation Mode Pumping regulation mode, normal or increased
Start Value Start value Allows system pressure drop
%, PSI before unit starts.
Config. 2nd Required Value Configuration of a second value
Off
Relay Configuration Relay configuration
Run Motor
Submenu Submenu offset: to enter push
Offset select for at least 1 second.
Offset Input Selection of offset input
Off
Level 1 Start level for offset 1
XX.X %
Level 2 Start level for offset 2
XX.X%
Intensity 1 Intensity of offset 1
XX.X%
Intensity 2 Intensity of offset 2
XX.X%
Submenu Submenu seq. control; to enter push select
Seq. Control at-least one second
Pressure Incr. Pressure increment at switching of additional
4 PSI pump
Pressure dec. Pressure decrement for consecutive pumps
4 PSI
Enable seq. ctl. Frequency limit enable sequence control
40.0 hz
Switch interval Time interval pump sequence change,
12h alternate time.