User guide

67
Help Windows
Window text Help Text
Window Pressure window
4%
Ramp Hysteresis Hysteresis
50%
Ramp 1 Ramp 1: fast acceleration time
4.0 Sec
Ramp 2 Ramp 2: fast deceleration time
4.0 Sec.
Ramp 3 Ramp 3: slow acceleration time
50%
Ramp 4 Ramp 4: slow deceleration time
50%
Max. Frequency Maximum output frequency
60.0 Hz range: 6 - 60 Hz
Min. Frequency Minimum output frequency
0.0 Hz (range: 0 - max. frequency)
Config. FMin Configuration behavior at
f->0 minimum frequency
Stop-Delay Time Delay for pump stop when
0 Sec. f->0 is chosen
Boost Boost, voltage boost applied on start-up
5.0% and shutdown.
SensorAdjust? Sensorzeroadjustment(press+)
Out of Range
Sensor Curve Sensor characteristic curve
Sensor Range Normalize to max. Sensor Value
20mA = 25.0 bar (362.6 PSI)
Mode: Mode: controller > pressure control;
Controller Actuator > frequency set point as ADC Value
Multicontroller > control of up to 4 pumps
t
t