User guide
2. Press the key until you reach the number
66. You will now be able to access all of the
alternate menus for all AQUAVAR controller
optional controls.
3. Press to advance the display to the next
window:
Thejogmodeisveryusefulbecauseitallows
you to check on the actual outgoing frequency
and system pressure. By pressing either or
the controller changes to manual, and you
can change the frequency to set any constant
speed. The AQUAVAR returns to normal auto-
maticoperationwhenyouleavethejogmode
window.
4. Continue to briefly touch the key to
scroll past all of the windows and submenus
until you reach:
5. Hold the key down for 2-3 seconds
until the display changes to:
6. Set the minimum pressure the system is
allowed to maintain before shutting down. For
example, if the set point for the system is 50
PSI, and the operator will allow anything
above 41 PSI, then the conveyor limit would
be set at 40 PSI. This function can also be
turned off by pressing until “disabled” is
shown.
26
Programming
t
0066
JOG MODE
t
t
*
SET CONVEYOR LIMIT
40 PSI
SUBMENU ERRORS
CONVEYOR LIMIT
Disabled
t
*
*










