iT T Commercial Water Systems Goulds Pumps AQUAVAR® Variable Speed Pump Control Installation Programming & Operation for Pump Mounted, V120 Software Controllers.
AQUAVAR Controller Owner’s Information Record AQUAVAR Controller Model_________________ Transducer Model_______________________ AQUAVAR Serial Number __________________ Transducer Rating_______________________ Date purchased __________________ Purchased from __________________ Pump Model __________________ Pump Code Number __________________ Software Version________________________ Program Record Please use the following to record the final values programmed into the AQUAVAR controller after in
Index ! System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Important Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Materials Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 1.
Index Operator Custom Features and Displays (continued) • Actual Value Increase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • Actual Value Decrease . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • Enable Sequence Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • Switch Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Design Typical Constant Pressure Systems Note Systems MUST be designed by qualified technicians only. The following diagrams show typical single pump and multi-pump systems using the AQUAVAR controller. Connection can be made directly to a water supply or water can be drawn from a supply tank or well. In the case of supply tanks and wells, level switches, (item 10) can be used to shut down the pumps when water is low.
! Safety Instructions Important: Read all safety information prior to installation of the AQUAVAR controller. Notice This is a SAFETY ALERT SYMBOL. When you see this symbol on the pump or in the manual, look for one of the following signal words and be alert to the potential for personal injury or property damage. DANGER Warns of hazards that WILL cause serious personal injury, death, or major property damage.
Safety Instructions 3. Installation and maintenance MUST be performed by properly trained and qualified personnel. 4. Review all instructions and warnings prior to performing any work on the AQUAVAR controller. 5. Any safety decals MUST be left on the AQUAVAR controller unit and pump. Note Inspect AQUAVAR controller for any damage after unpacking from shipping crates. Report any damage immediately to the carrier or distributor/dealer immediately. 6.
Safety Instructions Note Touching these components seriously endangers life! Voltages of up to 800 volts are possible (higher if there is a fault). Before removing the AQUAVAR controller drive top cover, the system must be disconnected from the main power supply. After switching off the power supply, you must wait at least 5 minutes before starting work on or inside the AQUAVAR controller drive head. This allows the capacitors in the circuit to be discharged by the discharge resistors. 8.
Installation Procedures Step 1- Identify Materials The following materials are provided with the AQUAVAR controller. Please familiarize yourself with each prior to installation. Part Quantity 1. AQUAVAR Controller 2. Fan Cover Assembly a. Screw M5x60 b. Motor mounting clamp 1 3 4 3. Pressure Transducer Assembly a. Pressure transducer (¼” NPT) b. Transducer cable gland c. Pressure transducer cable 30 ft.
Installation Procedures Step 2 - Mounting the AQUAVAR controller: WARNING The AQUAVAR controller Drive head and Pump must be totally disconnected from all power supply sources before beginning installation or repair. WARNING hazardous voltage can shock, burn or cause death. WARNING! Failure to disconnect Electrical power before attempting any maintenance can cause shock, burns, or death. Gasket Display changeable to 180º 1. The AQUAVAR controller drive head is supplied with all mounting hardware.
Electrical/Mechanical Specifications AQUAVAR Controller Technical Data: Aquavar Controller Part Nos.
Installation Procedures Electrical Connections WARNING WARNING! Failure to disconnect and lockout electrical power and wait five minutes for capacitor discharge before servicing Aquavar CONTROLLER can cause shock, burns, or death. hazardous voltage can shock, burn or cause death. Note Installation and maintenance must only be performed by properly trained and qualified personnel equipped with the proper tools. WARNING hazardous voltage can shock, burn or cause death.
Installation Procedures Electrical Connections continued Step 3 - Wiring the AQUAVAR controller to motor (Parts in the electrical fittings package will be required for this procedure.) Refer to Diagram 3 before proceeding. 1. Remove the three screws holding the top of the AQUAVAR controller. Carefully lift off the cover of the AQUAVAR controller. 2. Remove the screw holding the ground wire to the inside of the top of the AQUAVAR controller. Set cover aside. 3.
AQUAVAR Wiring Procedure – Single Phase Connections (2, 3, 5, 7½ and 10 HP) AQUAVAR® RS485 Interface Control Terminals Power Supply 1x230 VAC L=L1, N=L2 Motor Connection 3 Phase Out U, V, W – Three Phase Connections (5, 7½, 10 and 15 HP) AQUAVAR® RS485 Interface Control Terminals Power Supply 3x400 VAC L1, L2, L3 Motor Connection 3 Phase Out U, V, W Diagram 5 14
Installation Procedures Electrical Connections continued Note At this time, reference terminal block X1 locations, X1 #7 and #6, and X1 #5 and #4. If these connections are not being used for a low water switch or an external switch, they must be jumped as shown on Diagram 6. Note Use two core shielded cables for the thermal sensor and approved UL shielded wire power cable for the motor. 4. Thermal Sensor Wire Connections Locate the terminal block labeled X1 inside the AQUAVAR controller.
Installation Procedures Electrical Connections continued 5. Connections in Conduit Box Now that the wires have been routed through the port in the AQUAVAR controller. • Conduit and wires should be trial routed and cut to length at this time. After wire is routed through, insert connector through hole in conduit box and fasten with locknut. 6. Mount the thermistor into the conduit box so the metal side of the sensor will contact the motor shell when mounted.
Installation Procedures Electrical Connections continued 10. Now select one of the ports in the AQUAVAR controller to route the trans ducer cable. Cut to length and connect to locations X1 #2 and #3 as shown in Diagram 8. The brown wire is connected to X1 #3 and the white wire to X1 #2. Tighten strain relief.
Installation Procedures Electrical Connections (Line Reactors) Input Line Requirements Line Voltage See the Power and Current Ratings table for the allowable fluctuation of AC line voltage for your particular model. A supply voltage above or below the limits given in the table will cause the drive to trip with either an overvoltage or undervoltage fault. To verify power quality, consult your local power utility for a chart recorder.
Installation Procedures Electrical Connections continued 13. Route cable through strain relief and connect to the appropriate terminal block. Tighten strain relief. Warning Goulds Pumps strongly recommends the use of an input line reactor to safeguard your Aquavar from damage caused by high voltage spikes. These liNe reactors are available from your distributor and should be installed wherever uneven power supply is suspected.
Installation Procedures 17. Pump running signal and fault signal Pump running and fault signals such as lights may be wired to the AQUAVAR and set up in remote locations such as central control rooms. The fault signal can be wired to X2 pins 1, 2 and 3 and the pump running signal to X2 pins 4, 5 and 6. 18. Analog output of pressure or frequency A meter can be connected to X1 pins 10 and 11 for remote display of actual system pressure or motor running frequency.
Installation Procedures Instructions 1. Check all wiring. (Rotation of motor.) All motors used with the AQUAVAR controller are three phase. You will need to check the direction of rotation of the motor shaft. If you have followed all of the previous steps carefully, you should now be ready to apply power to the AQUAVAR controller unit. To change rotation of motor, switch any two output leads (U, V, W) on AQUAVAR with power disconnected. 2. Close discharge valve.
Installation Procedures t 6. Press the up arrow to turn on the AQUAVAR controller. Run Light on 7. Open the discharge valve slowly until the pump starts. Observe the rotation of the pump shaft or motor fan. If rotation of motor is reversed, disconnect input power on AQUAVAR. Then change any two leads on AQUAVAR output (U, V, W). See Diagram 5. 8. Close the discharge valve. 9. Press the down arrow t to turn off the AQUAVAR controller. (Inverter Stop - On —> Start) 10.
t t Programming Instructions 1. Check Power Light No Autostart - disable inverter 2. Press the down arrowt to advance the display to: 3. Press Select * Screen Inverter Stop - on->start to advance the display to: Required VALVE - xxx psi Note If “Inverter Locked” is displayed, the external on/off switch is in the off position or contacts at X1:4 and 5 are not jumped. t 4. Enter the pressure t you want the pump to maintain (constant pressure) for your system.
Programming * 6. Press to advance the display to: This display shows the last recorded error or fault encountered by the AQUAVAR controller. * * * * * Error 1 7. Press to advance the display to: This in the error which occurred before the last one. Error 2 8. Press to advance the display to: The error before error 2. Error 3 9. Press to advance the display to: The error before error 3. Error 4 10. Press to advance the display to: The error before error 4. Error 5 12.
Programming AQUAVAR Controller Program Flow Chart Single Pump Constant Pressure SW Ver. Date: Press • long ITT Ind. 50 PSI REQUIRED VALUE 50 PSI Auto-START ON ERROR 1 ERROR 2 ERROR 3 ERROR 4 ERROR 5 TOTAL RUN TIME 0000: 41 SAVE ?? –+v Diagram 12 WARNING Failure to save settings after programming results in loss of program values when power is removed! II.
Programming t 2. Press the key until you reach the number 66. You will now be able to access all of the alternate menus for all AQUAVAR controller optional controls. * 3. Press to advance the display to the next window: The jog mode is very useful because it allows you to check on the actual outgoing frequency and system pressure. By pressing either or t the controller changes to manual, and you can change the frequency to set any constant speed.
Programming To set timed protection: 7. Delay Time Enter the amount of time that the pump is allowed to run at maximum frequency after pressure begins to drop below the conveyor limit. This should never occur if the system has been properly sized and there are no leaks in the system. Note: This delay time is also applied to low suction pressure. delay time t Press the t to enter the number of seconds.
28 LEVEL 1 XX.X% Diagram 13 OFFSET – INPUT OFF LEVEL 2 XX.X% INTENSITY 1 X.X% ENABLE SEQ. CTL. 48.0 Hz ADC REFERENCE Local PUMP ADDRESS OFF ACTU. VALUE DEC. 0.15 PSI FREQU. – LIFTING 30.0 Hz SUBMENU RS485– Interface SUBMENU Seq. Control ACTU. VALUE INC. 0.35 PSI SENSOR– CURVE Linear SENSOR– ADJUST out of range BOOST 5.0% SUBMENU Offset RAMP HYSTERISIS 90% WINDOW 6% JOG-MODE 50.0 Hz 50 PSI PASSWORD 0000 ERROR 1 Auto-START ON REQUIRED VALUE 50 PSI ITT Ind.
Programming III. Single Pump - System Curve Compensation The AQUAVAR controller can automatically compensate for system friction losses due to increased flow. Tables are available in most pump catalogs indicating the amount of friction loss that can be expected in various sizes of pipe at different flow rates. Use these tables to determine the friction loss for the pipe size you are using at your maximum flow rate. H f = 100% %f WINDOW Diagram 15 shows a typical system curve.
Programming Entering compensation values: (system curve) For steps 1 through 4, refer to the flow chart. Instructions Screen * 1. From the main menu, hold down the key for 2-3 seconds until the display changes to: 2. t • Enter 66 by pressing the Password 0000 0066 Freq.- Lifting 30.0 hz This indicates the speed (flow rate) at which you want the pressure compensation to begin. On a 60 hz system, there is virtually no flow below 40 hz. Set this frequency with the up arrow.
31 LEVEL 1 XX.X% Diagram 15 OFFSET – INPUT OFF LEVEL 2 XX.X% INTENSITY 1 X.X% ENABLE SEQ. CTL. 48.0 Hz ADC REFERENCE Local PUMP ADDRESS OFF ACTU. VALUE DEC. 0.15 PSI FREQU. – LIFTING 30.0 Hz SUBMENU RS485– Interface SUBMENU Seq. Control ACTU. VALUE INC. 0.35 PSI SENSOR– CURVE Linear SENSOR– ADJUST out of range BOOST 5.0% SUBMENU Offset RAMP HYSTERISIS 90% WINDOW 6% JOG-MODE 50.0 Hz 50 PSI PASSWORD 0000 ERROR 1 Auto-START ON REQUIRED VALUE 50 PSI ITT Ind.
Programming Circulator applications On circulator pumps, the system curve can be automatically tracked through the use of a differential pressure transducer. This pressure transducer reads the outgoing discharge pressure and the incoming return pressure and compensates for differences in pressure as demand and speed increase. Programming is the same as just covered for the single transducer version. Data on the differential pressure transducer can be found in Appendix A. IV.
Programming Single Pump Constant Flow continued t 5. Use the to change the units to GPM if you are using a flow sensor or % if you are using the orifice plate. 6. Hold down the 7. Hold down the * * key until the screen: GPM key until the screen: Normalize 20 mA = 40 gpm 8. Enter either 37 psi for orifice plate application or the maximum flow range of your flow sensor in gpm. Screen Save ??? Saved t 9.
Programming V. Single Pump - Level Control Applications For drainage applications using a surface pump, the transducer is typically needed to measure pressure on the suction line. As the catch basin or tank empties, the pressure will decrease, and the pump needs to slow down and eventually stop. This is the opposite way the AQUAVAR controller would usually respond. To change to suction side measurement: 1.
Programming VI. Single Pump - Submersible Applications and Minimum Frequency It is possible to use the wall mounted version of the AQUAVAR controller with a submersible pump. *Never attempt to mount an AQUAVAR controller on the pump itself in these applications since the AQUAVAR controller is not designed to be submerged. The standard distance allowed between the pump and the AQUAVAR controller is up to 60 feet. If you need a longer connection, be sure to contact your distributor for a drive applied filter.
Programming * At the status window, hold the key until you reach the password screen. Enter the password. Use the * Minimum frequency 0 Hz key to advance to: t Use the and t to change to the desired minimum frequency (Example 35 Hz). Use the * PASSWORD 0066 Minimum frequency 35 Hz Config. fmin f -> Fmin key to advance to: t Use the andtarrow keys to change to: This allows the AQUAVAR to go down to the selected minimum frequency but not below it. Config.
Programming VII. Setting A Second Fixed Required Value The AQUAVAR controller can also be used in applications where the required value changes. As an example, a single pump system might be used to supply both water supply and irrigation needs on a farm. When the irrigation system is used, the pressure which needs to be maintained is higher than the pressure for normal water supply.
Programming Enter the submenu by holding the Enter the password and press the Press the t Use the * * * key. Itt Corporation 20 psi key. Password 0066 config. 2nd required value Off key until you see the screen: config. 2nd required value int and t arrows to change the selection to: Note The other possibilities (Ext. ADC-1, Ext ADC-U 0-10V, Ext ADC-V 2-10V) involve variable second values controlled by a second sensor. These are discussed in the next section.
Programming VIII. Variable Second Required Value In this section, we will cover the set up and programming of the AQUAVAR for a second sensor input. This sensor can be either a 4-20mA or 0/2-10V device such as a pressure transducer, flow transducer, heat sensor, etc. When connected to the AQUAVAR, the output of this second sensor becomes the new set point. As input from the second sensor changes, the set point will also change.
Programming Enter the submenu by holding the Enter the password and press the Press the * * * key. Itt Corporation 20 psi key. Password 0066 config. 2nd required value Off key until you see the screen: Use the andtarrows to change the selection to: EXT ADC-1 for 4-20mA input EXT ADC-U 0-10V for 0-10V input EXT ADC-U 2-10V for 2-10V input t Advance the display with the * * key to: config.
Offsets It is also possible to use second sensor input as an offset for the primary required value. An example would be locating the second sensor in a supply tank or well and setting an offset so that when the water level got too low, the pump discharge pressure setting would be reduced until the tank or well had recovered.
Programming analogue value 1 Level 1 % Level 2 % required value 75 PSI Intensity 1 - 10% 60 PSI Intensity 2 - 20% 45 PSI additional input 2 0%=4mA (0V/2V) 20% 80% 100%=20mA (10V) At Level 1 and Level 2, you enter the required value in percent from the Second Additional input (20%) and (80%). Intensity one and two depend on the Sensor range of the external value signal. The Intensity 1 that you have entered is valid until you reach Level 1, after reaching Level 1 the Required Value has no offset.
Programming Press * Intensity 1 +xx.x% key to advance to: Use the andtarrow keys to enter the % of the Intensity 1 -10.0% required value you want to increase or decrease when the second sensor input is below Level 1. The chart on the previous page uses -10% as an example. This represents an application where the second sensor is in a well or tank.
Programming Electrical Connection Dry contacts are available to connect a relay at X2/4-X2/5 (normally closed) or X2/6-X2/5 (normally open). The relay is located between main line power and the second, full speed, pump. NOTE: 250 VAC, 1 amp is maximum for the above contacts. In this method, the second (slave) full speed pump may be either single or three phase with any motor enclosure. The main pump (AQUAVAR controlled) must still be a three phase motor and TEFC if the AQUAVAR is to be pump mounted.
Programming * * submenu synch. control Hold the key again to return to the sequence control submenu. Hold the * t Press the submenu sequence control Save ??? key to advance to: t Hold the key to return to the synchronous control submenu. +t Save ??? Saved andtarrows until: Using the above settings, when there is system demand, the AQUAVAR pump will start first and maintain pressure until it reaches 58 Hz. At that point, the relay will start the slave pump at full speed.
Programming X. Multiple Pump Constant Pressure and System Curve Compensation When two, three, or four AQUAVAR controller controlled pumps are connected in a system, they can be programmed to work together to maintain system pressure up to the maximum flow rate of all pumps combined. As the first pump reaches its maximum speed and flow, the second pump will automatically turn on (and so on).
Programming Multiple Pump Constant Pressure... continued Generally, a slight pressure drop is allowed on the first pump before the next is started. This allows for brief system fluctuations without pump cycling. Once the next pump starts, however, you will want the system to resume its normal set pressure. 7 H ∆P 6 ∆P 5 4 P1 P1 + P2 P1 + P2 + P3 3 5. To do this, enter the amount of pressure drop you will allow before the next pump starts.
Programming Multiple Pump Constant Pressure... continued Screen 8. Enter the value required. actual valUe Inc. 0003 PSI * actual valUe Dec. 000 psi • Press to advance to the next screen: • Enter the PSI drop before the next pump starts. Use this value for each pump in the AQUAVAR controller system. 9. Enable Seq. Ctl. 60.0 hz This tells the next pump when the preceding pump has reached its maximum speed. • Press * actual valUe dec. 0002 PSI Screen Enable Seq. Ctl. 60.0 hz.
Programming Multiple Pump Constant Pressure... continued Source Required Value The next screen refers to the use of a second input signal for changing the required value. This was discussed in Section VIII. If a second sensor or switch is used, you must tell SOURCE REQUIRED VALUE the AQUAVAR which pump has the connection. Use ADR1 the and t keys to select. ADR1, ADR2, ADR3 or ADR4. If you are not using a second sensor, leave this set to “off”.
Programming Multiple Pump Constant Pressure... continued 12. Pump Address In this section you will give the pump an address number. Generally, the first pump programmed will be number 1, the second will be number 2, and so on. The purpose of this is to help the AQUAVAR controller sequence the start and stop activity of the pumps in the system including the selection of lead and lag pumps.
51 LEVEL 1 XX.X% Diagram 17 OFFSET – INPUT OFF LEVEL 2 XX.X% INTENSITY 1 X.X% ENABLE SEQ. CTL. 48.0 Hz ADC REFERENCE Local PUMP ADDRESS OFF ACTU. VALUE DEC. 0.15 PSI FREQU. – LIFTING 30.0 Hz SUBMENU RS485– Interface SUBMENU Seq. Control ACTU. VALUE INC. 0.35 PSI SENSOR– CURVE Linear SENSOR– ADJUST out of range BOOST 5.0% SUBMENU Offset RAMP HYSTERISIS 90% WINDOW 6% JOG-MODE 50.0 Hz 1 92 PSI PASSWORD 0000 ERROR 1 Auto-START ON REQUIRED VALUE 50 PSI ITT Ind.
Programming XI. Multiple Pump - Pump Protection The AQUAVAR controller can protect the pump by shutting it off in low/no suction or run out conditions. Note Low/no suction protection depends on the installation of a suction line pressure switch or float switch for a tank. This switch is connected to the AQUAVAR controller as described earlier in the electrical installation section. The cut out setting for a suction pressure switch should be greater than the maximum NPSH required by the pump.
Programming Multiple Pump Pump Protection... continued Instructions Error Reset Turning this control on will enable the AQUAVAR controller to retry its operation five times when a fault condition occurs. Turning the control to “off” means that the AQUAVAR controller will shut down the first time a fault occurs. • Press * • Use the to advance the display to: Screen Error Reset t 3. t to select the mode you want.
Operator Custom Features and Displays Refer to the overall Program Flow Chart for the location of the following operator custom features. To access a particular feature: • Enter the password (66) at the Main Menu. * • Scroll to the selected feature by using the “ ” key. Other features have already been discussed in the application set-up instructions described earlier. Note Custom features are pre-programmed to default settings.
Operator Custom Features and Displays Ramp 1 This ramp is the fast run up time used when the pump first comes on and is trying to reach the set point. The normal set point for this ramp is 4 seconds for the horse power range 2 through 15 hp. For versions with higher horsepowers, 20 hp and above, the setting should be 10 seconds minimum. A setting which is too fast may overload the inverter. A setting which is too slow tends to cause uneven outgoing pressure (pressure drops).
Operator Custom Features and Displays Minimum Frequency Settings between 0 and 50 Hz are possible. When a minimum frequency is set, the AQUAVAR will not run the pump below this speed. See the section on submersible pumps. Config. F Min This setting allows you to configure a minimum frequency in one of two ways. If you select “f>0”, the inverter will go down to the minimum frequency and then continue running at that level for the delay time (see next features).
Operator Custom Features and Displays Controller - Used for a single AQUAVAR controlled pump Multicontroller - Used where several AQUAVAR pumps are connected via RS485 Synchronous Controller - Used for multipump systems where all pumps will run at the same frequency. Actuator - Used if you have an external (PID) controller. In this mode the internal controller is turned off. The output frequency changes proportionally based on sensor input (X1/2) and the following chart.
Operator Custom Features and Displays Regulation Mode The “Normal” setting increases the output speed with falling signal (constant pressure in discharge). The “Inverse” setting decreases the output speed with falling signals (suction control). Submenu Sequence Control - for further information see Section V Use this menu to allow starting and stopping of up to 4 pumps with the RS-485 communication port. The following setup items allow the user to determine when the pumps will start and stop.
Operator Custom Features and Displays Synchronous Limit To deactivate synchronous control, set this value below 0 HZ. This will be the lowest speed that multiple pumps will operate prior to switching off the last pump in sequence. For 60 Hz systems using synchronous mode, this would normally be set to 40 Hz. This window is also used for the stop value of a slave pump. Synchronous Window This is a frequency offset that increases the synchronous limit that each lag pump is stopped at.
Operator Custom Features and Displays ADC Reference This setting tells the unit where to look for the actual value signal. Set to “LOCAL” if the actual value is obtained from a 4-20mA transmitter wired to the unit’s actual value input terminals (X1: 2, 3). Set to “REMOTE” if the actual value is obtained from the RS-485 port via a remote device. Default is local. Frequency Lifting Allows modification of the required pressure to accommodate for system frictional losses due to increased flow.
Operator Custom Features and Displays Test Run The AQUAVAR controller can carry out a test run of the pump either automatically or manually. For automatic settings, enter the number of hours you want to elapse between the last pump shut down and the test. Possible settings are between 10 and 100 hours. When the time has elapsed, the pump will automatically turn on at 50% of maximum frequency (normally 30 hz) for 20 seconds and then turn off again.
Operator Custom Features and Displays Operating Hours This counter displays the total amount of time that the AQUAVAR controller drive head has operated, (whether the pump was running or not). This time can be reset to zero by pressing the up and down arrows at the same time for 25 seconds. Total Run Time This display shows the total run time of the pump motor in hours and minutes. This display resets automatically when Operating Hours is reset.
Repair of Faults and Errors Repair of Faults and Errors WARNING Disconnect power from the AQUAVAR controller before connecthazardous voltage ing the faults to avoid potential for automatic pump restart. WARNING Lack of Water This error message will be displayed when a switch has indicated that the incoming water pressure or water level in a suction tank falls below the required NPSH of the pump.
Repair of Faults and Errors Overloaded The most common problem is incorrect program settings causing the pump to exceed its duty range. When this happens, the AQUAVAR controller will shut down the system to protect the pump and motor. Check programming, maximum system requirements, pump blockage due to solids, broken mechanical seal, defective non-return valve, pump motor run in reverse, motor amps, and pump selection.
65 LEVEL 1 XX.X% Diagram 19 OFFSET – INPUT OFF LEVEL 2 XX.X% INTENSITY 1 X.X% ENABLE SEQ. CTL. 48.0 Hz ADC REFERENCE Local PUMP ADDRESS OFF ACTU. VALUE DEC. 0.15 PSI FREQU. – LIFTING 30.0 Hz SUBMENU RS485– Interface SUBMENU Seq. Control ACTU. VALUE INC. 0.35 PSI SENSOR– CURVE Linear SENSOR– ADJUST out of range BOOST 5.0% SUBMENU Offset RAMP HYSTERISIS 90% WINDOW 6% JOG-MODE 50.0 Hz 50 PSI PASSWORD 0000 ERROR 1 Auto-START ON REQUIRED VALUE 50 PSI ITT Ind.
Help Windows Help Windows * t ? You can access a help display at any time by pressing and holding the “ “ and arrow keys at the same time. This will change the second line of the window to a “running” text which provides more information about the window function. The following list shows the normal window text and the available help text. Window text No Autostart Disable Inverter Help Text ITT Corporation X.XX PSI Spanish > Inc.; English > Dec; French > Select Required Value x.
Help Windows Window text Help Text Window 4% Pressure window Ramp Hysteresis 50% Hysteresis Ramp 1 4.0 Sec Ramp 1: fast acceleration time Ramp 2 4.0 Sec. Ramp 2: fast deceleration time Ramp 3 50% Ramp 3: slow acceleration time Ramp 4 50% Ramp 4: slow deceleration time Max. Frequency 60.0 Hz Maximum output frequency range: 6 - 60 Hz Min. Frequency 0.0 Hz Minimum output frequency (range: 0 - max. frequency) Config.
Help Windows Window text Help Text Regulation Mode Pumping regulation mode, normal or increased Start Value %, PSI Start value Allows system pressure drop before unit starts. Config. 2nd Required Value Configuration of a second value Off Relay Configuration Run Motor Relay configuration Submenu Offset Submenu offset: to enter push select for at least 1 second. Offset Input Selection of offset input Off Level 1 Start level for offset 1 XX.X % Level 2 Start level for offset 2 XX.
Help Windows Window text Help Text Submenu Synch. control Submenu: synchronous regulation; to enter push select at least one second. Synchron limit 35.0 Hz Frequency limit to enable the synchronous regulation Synchron window 5.
Help Windows Window text Help Text Test Run Man. (Inc + Dec) Start test run with Increase + Decrease Test Frequency 30.0 hz Test frequency Boost Test Run 5% Submenu Error Test boost Submenu: errors; to enter push select at least one second Conveyor Limit Value at which pump system shall be deactivated Delay 2 sec Error Reset On Enter a time the pump is allowed to run after a suction line sensor has activated, or conveyor limit has been reached.
Appendix A Pressure Transducer Data Series 1200 Gems Type Specifications Measuring Range (FS): Over-Pressure (PMAX): Class of protection: .52 bar 10 bar 2 bar 40 bar IP 65 (Nema 4) 25 bar 100 bar (other ranges upon request) Type Sealed gauge: Output-Signal: Supply: 4-20mA; 2 wire 7-35 VDC Linearity: Stability: Total Error: 0.5% FS 0.2% FS max. 2% FS Operating Temperature: -22°F to 260° F Material: Body and diaphragm: 17-4 PH 3.45 1⁄4” 1.
Appendix A Differential Pressure Transmitter Screw joint and cover: 44 Series PD-39S P- The sensors of this differential transmitter are two piezoresistive silicon pressure sensors, mounted on a tape (TAP), freely floating in an oil chamber. The pressure is transferred to the sensor by a separating steel diaphragm in the oil chamber. 60 26 P+ = 95 40 Plug: mPm 193 incl.
Appendix A Pressure Transducer Data Model Delta 692 Differential Pressure Transducer and Orifice Plate Specifications Range (FS)” Over Pressure (PMAX) Signal over Range Power Supply E1 Connection Hydraulic connection Linearity Stability Operating Temperature Storage Temperature Materials Standard 80096 ND 2, 5 bar - 37 PSI 12 bar - 177 PSI 4... 20mA; 2 wire 9... 33 volts DC DIN-plug 43650 1 2 3 4 5 1 3 P1 4 P2 5 2 Diagram 22 R 1/8" tip± .25%FS; max.±.5%FS tip± .1%FS; max.±.
Appendix B AQUAVAR Controller Drive Head Technical Data and Terminals Instructions: Use this supplement for installation and wiring of AQUAVAR models 04168321, 04168331, 04168371, 04168491, 04168501 and 04168511.
Appendix B AQUAVAR Controller Drive Head Technical Data and Terminals continued Air Pollution: Altitude: Approvals: Enclosure: Control: Lead/Lag: Inverter: Terminals: X1 1 2 3 4 5 6 7 8 Minor amounts of dust and dirt are permitted. Excessive dust, acids, corrosives and salts must be avoided. 3300’ above sea level, without derating. Derate 2% each 1000’ above 3300’.
Appendix B AQUAVAR Controller Drive Head Technical Data and Terminals continued 9 10 11 12 13 14 Thermoswitch return connection. Ground connection for analog output. Analog output connection 0 - 10 Vdc, maximum 2 mA. Can be used to connect an outside meter or display panel to display actual pump running frequency or pressure as selected on the Analog Out part of the program. Current signal input 4-20mA. Voltage signal input 0-10V or 2-10V. Digital input.
Appendix C Interference Suppression Measures Introduction Electrical/electronic devices are capable of influencing or disturbing each other through connecting cables or other metallic connections. Interference suppression measures (electromagnetic compatibility) consists of two elements: interference resistance and interference emission.
Appendix C • Take care not to damage the shield cross section when connecting it to the continuing lines. This raises the RF resistance of the shield and radiates rather than discharges the RF energy traveling on the shield. Shields, particularly those on control cables, must not be routed through pin contacts (plug connectors). • When shielded cables must pass through a plug connection, use the metallic hand guard of the plug for the continuation of the shield.
Appendix D The final difference is the addition of a DIP switch SW4 which can be used to select a lower switching frequency. This could be used to improve the motor efficiency of submersible pumps, and overall power consumption. This will also increase the audible motor noise. Before changing this switch the AQUAVAR controller must be disconnected from the power supply.
Operating Instruction Technical Data - Frequency Inverter Output voltage: Max. frequency: Min. frequency: Electrical Efficiency: Three phase unit: 3 x 400-460 V AC See: max. Frequency 60 Hz 0 - f-max. (0 Hz or Fmin setting) > 95% Note If the motor and control unit are assembled separately keep the motor cable as short as possible in order to avoid electromagnetic emissions and capacitive currents. The length may not exceed 30 m (60 ft.) and a shielded cable must be used.
Notes 81
Notes 82
iT T Commercial Water Systems GOULDS PUMPS LIMITED WARRANTY This warranty applies to all Aquavar CPC controllers manufactured by ITT Corporation. Any part or parts found to be defective within the warranty period shall be replaced at no charge to the dealer during the warranty period. The warranty period shall exist for a period of twenty-four (24) months from date of installation or thirty (30) months from date of manufacture, whichever period is shorter.