Without An Analog Signal Generator
!
·
Multi Zone Pulse Flow Sensor Connected to an Analog Transmitter
!
2.13.5.1 Calibrating with an Analog Transmitter (Model 310)
!
An Analog Transmitter (such as the Model 310 normally used by Flowtronex®) converts the pulse
output of the 220B flow meter to a 4 to 20 mA analog signal. The Model 310 is calibrated at the factory
to provide specific full scale outputs based on pipe size. Use the following table to determine
the
correct
size.
!
!
Pipe
Size
(Schedule
40)
Max GPM @ 20 mA
2
inch
200
2.5
inch
250
3
inch
400
4
inch"
800
6
inch"
1400
8
inch"
3000
10
inch"
5500
12
inch"
9000
14
inch"
11,500
!
!
There are two ways to calibrate the flow, with or without a 4-20 mA signal generator.
!
2.13.5.2 Calibration Procedure with a Signal Generator
!
Use the following procedure to calibrate a 220B Flowmeter with a Signal Generator. Information is
entered on the Calibration screen page 3.