Owner's manual
© 2013 Flowtronex
92
Omron Touch-Screen Display
!
!
!
!
!
1) Turn speed pot fully counter clockwise to its minimum setting.
!
2) View and average the value in Raw Data (:29), and enter in CH1 min (:69), and MinIn (:79).
!
3) Turn speed pot fully clockwise to its maximum setting.
!
4) View and average the value in Raw Data (:29), and enter in MaxIn (:89).
!
5) Enter 6400 in MinOut (:99).
!
6) Enter 32400 in MaxOut (:109).
Calibration is complete.
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the N Register Access screen.
!
·
Optionally, press the up
(
▲
)
or down arrow
(
▼
)
keys to access the other eight calibration
screens.
!
2.13.5 220B Flowmeter with Analog Transmitter
!
To set up a 220B Flow Meter with an Analog Transmitter, access the Register Access screen by
pressing the Register Access key on the Main Menu.
!
!
!
·
Press the N Register Menu touch key on the Register Access screen to open the N Register
Access screen.