Owner's manual
© 2013 Flowtronex
How Do I?
81
!
!
!
!
!
!
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the previous screen, Calibration page 4.
!
2.13.2.2 220B Flowmeter
!
Calibrating a single zone pulse flow sensor
!
A pulse type flow sensor uses a span and offset value based on flow meter spool pipe size to calibrate
it. See following table:
!
Pipe
Size
(Schedule
40)
Span
(to be entered in
N52:0)
Offset
(to be entered in
N52:1)
3
inch
436
–06
4
inch
834
–23
6
inch
2157
–26
8
inch
4009
–28
10
inch
6453
–31
12
inch
9737
–36
14
inch
11610
–38
!
Access the Register Access screen by pressing the Register Access key on the Main Menu. The
calibration screens are accessed from the Register Access screen by pressing the N Register Menu
touch key.