Calibration Procedure without a signal generator
!
Without a signal generator, the calibration procedure is much more difficult, less accurate, and
requires a calculator.
!
1) With no flow, record the counts in raw data (:22) and enter that value in Min Raw (:62) and MinIn
(:72).
!
2) Enter 0 in MinOut (:92).
!
3) Run pump station in as close to a full flow condition as possible. The higher the flow, the more
accurate the calibration.
!
4) Record the counts in raw data (:22) and enter that value in MaxIn (:82).
!
5) Measure mA signal in series with positive input to the analog board. Write this number down.
!
6) Subtract 4 mA from this reading. Write this number down.
!
7) Use the Krohne Meter Calibration chart above. Select the correct Krohne Meter size. Go to the
Max GPM at 20 mA column and record that number.
!
8) Divide the max GPM by 16 and write down that number.
!
9) Multiply that number (GPM per mA) by the adjusted mA reading from step 5.
!
10) Enter this number in MaxOut (:102).
!
!
Example:
You have a pump station with an 8 in flow meter spool. Therefore the maximum GPM @ 20 ma is
3000 GPM.