Omron Touch-Screen Display
!
!
!
!
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the previous screen, N Register Access.
!
Calibrating a Krohne flow meter
!
A Krohne flow meter is an analog device. Calibration is very similar to the 220B with Analog
Transmitter (Model 310), except that the Krohne meter has a different table to use to determine the
maximum GPM @ 20 mA.
!
!
Krohne Meter
Size
(Inches)
Max
GPM
@ 20
mA
1
60
1.5
135
2
240
3
550
4
970
6
2200
8
3900
10
6100
12
8800
14
12000
!
There are two ways to calibrate the flow, with or without a 4-20 ma signal generator. It is a lot easier
with the signal generator.
!
Calibration Procedure with a signal generator
!
1) With no flow, record the counts in raw data (:22) and enter that value in Min Raw (:62) and MinIn
(:72).
!
2) Remove the Krohne meter input wires at the PLC and connect your signal generator.
!
3) Generate a 20 mA signal.
!
4) Record the counts in raw data (:22) and enter that value in MaxIn (:82).
!
5) Disconnect the signal generator and reconnect the Krohne meter wiring.
!
6) Enter 0 in MinOut (:92).
!
7) Use the Krohne Meter Calibration chart above. Select the correct Krohne Meter size. Go to the
Max GPM @ 20 mA column and record that number in MaxOut
(:102).