Omron Touch-Screen Display
!
!
!
!
!
1) Close the ball valve that isolates the particular pressure transducer that you are trying to calibrate.
!
2) Disconnect the black tubing at the pressure transducer.
!
3) View and average the raw data value that is in MinRaw (:20 or :21). Enter data in MinIn (:60 or
:61) and in MinIn (:70 or
:71).
!
4) Enter 0 in MinOut (:90 or :91).
!
5) Hold the disconnected end of the black tubing, crack open the pressure transducer ball valve to
bleed the air out of the tube, and reconnect to the pressure transducer.
!
6) Fully open the pressure transducer ball valve.
!
!
Warning:
Ensure that you point the tubing discharge away from all electrical components.
!
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the N Register Access screen.
!
·
Optionally, press the down arrow
(
▼
)
to return to display Calibration page 2.
!
2.13.1.2 Calibrating Maximum Pressure
!
Calibration page 1 shows the settings for Channel 0, the downstream transducer and Channel 1 the
upstream transducer. Values are shown in PSI. Use the following procedure to calibrate maximum
pressure.
!
!
!
There are two ways to calibrate the maximum pressure. Either apply a 20 mA signal using a (signal
generator) to the correct channel on the PLC, or turn on the pump station and build the upstream or
downstream pressure to setpoint pressure.
!
Calibrating the maximum pressure using the signal generator