Owner's manual
© 2013 Flowtronex
How Do I?
59
!
!
!
!
!
!
!
!
Note:
Flow setpoint to stop combo x are examples only. They are calculated based on
80% of the previous combo's maximum flow.
!
!
·
Use the table below for these calculations and enter the values in GPM for Max Flow, Stop Combo
x registers N:23:1 to N:23:8 as needed.
!
!
Combo
Number
!
Pump
Size
!
Full Flow
of
Previous
combo
!
Flow Setpoint
to
Stop
Combo
!
1
!
20
HP
!
0
GPM
!
0.8 X 0 GPM = 0 GPM
!
2
!
50
HP
!
200 GPM
!
0.8 X 200 GPM = 160 GPM
!
3
!
75
HP
!
500 GPM
!
0.8 X 500 GPM = 400 GPM
!
4
!
75 HP and 50 HP
!
750 GPM
!
0.8 X 750 GPM = 600 GPM
!
6
!
75 HP, 50 HP, and 20HP
!
1250 GPM
!
0.8 X 1250 GPM = 1000 GPM
!
!
·
Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.
Enter or edit the value. (See also, Calculator/Keypad.)
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the Register Access screen.
!
·
Press the down arrow
(
▼
)
to display the VFD Bypass screen page 1.