The values on the VFD Bypass screen page 1 are similar to but not identical to those used for normal
operation. They rarely would require changing. The default values are shown.
!
·
N21:33 is the pressure below setpoint to start combo 1. Default is 005 PSI
!
·
N21:34 is the delay time to start combo 1. Default is 000 Sec.
!
·
N21:35 is the pressure above setpoint to stop combo 1. Default is 005 PSI
!
·
N21:36 is the delay time to stop combo 1. Default is 005 Sec.
!
·
N21:37 is the pressure below setpoint to start combo 2. Default is 012 PSI.
!
·
N21:38 is the delay time to start combo 1. Default is 010 Sec.
!
·
Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.
Enter or edit the value. (See also, Calculator/Keypad.)
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the Register Access screen.
!
·
Press the down arrow
(
▼
)
in the bottom right corner of the screen to open the next screen,
VFD Bypass page 2.