Omron Touch-Screen Display
!
!
!
!
!
!
!
!
Note:
The values on Timer Access page 1 and page 2 are set at the factory and should
not require changing.
!
!
·
Enter a time in seconds in the T4:04 Pre field. Default delay time is 45 seconds for the Pump
anti-cycle fault.
!
·
Enter a time in seconds in the T4:16 Pre field. Default delay time is 15 seconds for the Long start
inhibit fault.
!
·
Enter a time in seconds in the T4:38 Pre field. Default delay time is 3 seconds for the Short start
inhibit fault.
!
·
Enter a time in seconds in the T25:25 Pre field. Default delay time is 15 seconds for the Delay til
lamp test fault.
!
·
Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.
Enter or edit the value. (See also, Calculator/Keypad.)
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the Register Access screen.
!
·
Press the down arrow
(
▼
)
in the bottom right corner of the screen to open the next screen, Timer
Access page 2.