Owner's manual

© 2013 Flowtronex
How Do I?
37
!
!
!
!
!
!
!
The second Safety registers screen is devoted to optional safeties.
!
·
N70:6 is the delay time for a Loss of Prime fault. In this case, a probe is placed in the suction
piping. The default value is 0 seconds.
!
·
N70:7 is the delay time for a Low Inlet Pressure fault. Normally a pressure switch is installed in the
suction piping. The default value is 20 seconds.
!
·
N70:8 is the delay time for a Flow Over-demand fault. The default value is 180 seconds.
!
·
N71:8 is the flow at which a Flow Over-demand fault occurs. The default value is your total station
flow plus 20%.
!
·
N70:9 is the delay time for a Filter Fault. The default value is 0 seconds.
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the Register Access screen.
!
·
Press the down arrow
(
)
in the bottom right corner of the screen to display the Safety
registers page 3.