Owner's manual

© 2013 Flowtronex
How Do I?
33
!
!
!
!
!
the value entered in N21:9 (123 PSI in this example), ,then the pump is retired.
!
Note:
The second (and higher) main pump is normally not controlled by the VFD. Therefore, the value
in N21:13 is usually set to 30 PSI. In the case of multiple VFDs, the value would be -2.
!
·
N21:10 defines the delay time before the second pump stops, once the stop pressure is reached.
This is normally set to 10 seconds.
!
·
N21:11 defines the pressure below normal setpoint pressure when the third pump (normally the
second main pump, but not always) starts automatically.
!
For example, if your normal setpoint pressure is 120 PSI and you enter 15 in N21:11, the second
pump comes on at 105 PSI.
!
·
N21:12 defines the delay time before the third pump starts, once the start pressure is reached.
This is normally set to 0.
!
·
N21:13 defines the pressure above normal setpoint pressure when the third pump (usually the
second main pump, but not always) stops automatically.
!
For example, if your normal setpoint pressure is 120 PSI and you enter 5 in N21:13, the first
pump retires at 125 PSI.
!
Note:
The second (and higher) main pump is normally not controlled by the VFD. Therefore, the value
in N21:13 is usually set to 30 PSI. In the case of multiple VFDs, the value would be -2.
!
·
N21:14 defines the delay time before the third pump stops once the stop pressure is reached. This
is normally set to 90 seconds.
!
·
Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.
Enter or edit the value. (See also, Calculator/Keypad.)
!
!
Note:
Use the values defined for combo 3 when the number of combos exceeds 3.
!
!
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the Register Access screen.
!
·
Press press the down arrow
(
)
in the bottom right corner of the screen to display
Combo setpoints page 4.
!
Three auxiliary setpoints can be used and set up on page 4, Aux Setpoints screen.