Owner's manual
© 2013 Flowtronex
32
Omron Touch-Screen Display
!
!
!
!
!
the value entered in N21:9 (123 PSI in this example), then the pump is retired.
!
·
N21:6 defines the delay time before the first pump stops once the stop pressure is reached. This
is normally set to between 5 and 10 seconds.
!
·
N21:7 defines the pressure below normal setpoint pressure when the second pump (normally the
first main pump, but not always) will start automatically.
!
For example, if your normal setpoint pressure is 120 PSI and you enter 15 in N21:7, the second
pump comes on at 105 PSI.
!
·
N21:8 defines the delay time before the first pump starts, once the start pressure is reached. This
is normally set to 0.
!
·
Tap the value field next to any of these registers and the calculator/keypad pops-over the screen.
Enter or edit the value. (See also, Calculator/Keypad.)
!
·
To define combos 2 and 3+, press the down arrow
(
▼
)
in the bottom right corner of the screen
to display Combo setpoints page 3.
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the Register Access screen.
!
!
!
·
N21:9 defines the pressure above normal setpoint pressure when the second pump (usually the
first main pump, but not always) will stop automatically.
!
For example, if your normal setpoint pressure is 120 PSI and you enter 5 in N21:9, the second
pump retires at 125 PSI.
!
Note:
If this is the first main pump, and it is controlled by a VFD, the value needs to be -2. If station
flow is less than 20 GPM and the station pressure is at the normal setpoint (125 PSI in this
example) the PLC does a speed test to determine whether to shut the pump down. A speed test
means that the VFD slows down to minimum speed. If the station pressure remains at or above