Enter the setpoint in PSI for Lockout #1 in the N20:3 register. A common setpoint is 120 PSI.
!
Enter the maximum combo used for Lockout #1 in the N20:4 register.
!
Enter the setpoint in PSI for Lockout #2 in the N20:5 register. A common setpoint is 120 PSI.
!
Enter the maximum combo used for Lockout #1 in the N20:6 register.
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the Register Access key.
!
·
Press the down arrow
(
)
in the bottom right corner of the screen to open the next
screen, Combo setpoints page 2.
!
!
!
·
N21:3 defines the pressure below normal setpoint pressure when the first pump (usually the
PM
pump, but not always) starts automatically.
!
·
N21:4 defines the time delay before the first pump starts, once the start pressure is reached. This
is normally set to 0.
!
For example, if your normal setpoint pressure is 120 PSI and you enter 10 in N21:3, the first
pump comes on at 110 PSI.
!
·
N21:5 defines the pressure above normal setpoint pressure when the first pump (usually the
PM
pump, but not always) stops automatically.
!
For example, if your normal setpoint pressure is 120 PSI and you enter 5 in N21:5, the first
pump retires at 125 PSI.
!
Note:
If this is the first main pump, and it is controlled by a VFD, the value needs to be -2. If station
flow is less than 20 GPM, and the station pressure is at the normal setpoint (125 PSI in this
example), the PLC does a speed test to determine whether to shut the pump down. A speed test
means that the VFD slows down to minimum speed. If the station pressure remains at or above