Owner's manual

© 2013 Flowtronex
146
Omron Touch-Screen Display
!
!
!
!
!
00000100 is Pump 2 and would be entered as 4 in B85:5.
!
00001000 is Pump 3 and would be entered as 8 in B85:5.
!
00010000 is Pump 4 and would be entered as 10 in B85:5.
!
00100000 is Pump 5 and would be entered as 20 in B85:5.
!
01000000 is Pump 6 and would be entered as 40 in B85:5.
!
10000000 is Pump 7 and would be entered as 80 in B85:5.
!
·
B85:11 is the delay time for an individual booster pump High Discharge Pressure fault. The default
value is 60 seconds.
!
·
B85:12 is the delay time for a booster pump start. The default value is 5 seconds.
!
·
B85:13 is the delay time for an individual booster pump Low Discharge Pressure fault. The default
value is 300 seconds.
!
·
B85:14 is the time delay until the booster pump stops is equipped with a limit switch. The default
value is 30 seconds.
!
·
Tap the value next to any of these registers to open the calculator/keypad. Enter or edit the value.
(See also, Calculator/Keypad.)
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the B Register Access.
!
·
Press the down arrow
(
)
to advance to the Booster Status page 2 screen.
!
!
!
The parameters shown on the Booster Status page 2 screen are read-only
values.
!
·
The main zone displays a 0 for Off, or a 1 for Run.
!
·
The Booster Run is either ON or OFF.