Owner's manual
© 2013 Flowtronex
How Do I?
125
!
!
!
!
!
!
!
The white boxes to the right are enabling bits that show if the bit is enabled or disabled. As shown on
the screen above, a green-block one (1) indicates the bit is enabled and a zero (0) shows the it is not
enabled. Tap on each bit to toggle the bit on or off.
!
·
B3:01 /1 is set to 0 for Run Relay Mode on new VFDs.
!
·
B3:02 /2 should always be set to 0 for True Max Speed. False Max Speed can be used for
troubleshooting purposes.
!
·
B3:02 /4 is for a jockey pump and if enabled allows the jockey to come back on during shut down.
!
·
Tap the bit sum field and the calculator/keypad pops-over the screen. Enter or edit the value. (See
also, Calculator/Keypad.)
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the B Register Access screen.
!
2.23 View My Combo Logic
!
Viewing the password protected Combo Logic screens is a very useful tool when troubleshooting
pump start and/or stop problems. This screen can be accessed in two different ways:
!
·
From the Main Menu by tapping the Combos touch key.
!
·
From the Register Access screen by pressing the B Register Menu touch key to open the B
Register Access screen and tapping the B40:xx Combos touch key.
!
2.23.1 Access Combo Table from the Main Menu
!
You can access the Combo Menu and the two Combo Table screens from the Main Menu. The
screens let you to select the pumps enabled in a combo.