Omron Touch-Screen Display
!
!
!
!
!
·
Optionally, press the down arrow
(
)
to advance the next Calibration screen.
!
·
See also, Calibration Procedure with a Signal Generator.
!
2.13.5.4 Calibrating Multiple Zone Pulse Flow Sensors
!
The calibration procedure for calibrating multiple one pulse flow sensors connected to an analog
transmitter is identical to the single zone procedure with the exception that zone 1 is now on channel 5
instead of channel 2, zone 2 is on channel 6, and zone 3 is on channel 7 (if applicable). No further
calibration is required. Channel 2 will display the total flow for all zones. Duplicate the single zone
calibration procedure from earlier in this section, but ensure that you use the correct channel.
!
!
!
·
Tap the value next to any of these registers to open the calculator/keypad. Enter or edit the value.
(See also, Calculator/Keypad.)
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the previous screen.
!
·
Optionally, press the down arrow
(
)
to advance the next Calibration screen.
!
·
See also, Calibration Procedure with a Signal Generator.
!
2.14 Define My Start / Stop Features
!
You can access the Start/Stop Features screen and define your primary pumps start/stop
characteristic under normal conditions and when using VFD Bypass by pressing the Register Access
touch key on the Main Menu and opening the Register Access screen.