Owner's manual
© 2013 Flowtronex
How Do I?
97
!
!
!
!
!
!
!
1) With no flow, record the counts in raw data (:22) and enter that value in Min Raw (:62) and MinIn
(:72).
!
2) Enter 0 in MinOut (:92).
!
3) Run pump station in as close to a full flow condition as possible. The higher the flow, the more
accurate the calibration.
!
4) Record the counts in raw data (:22) and enter that value in MaxIn (:82).
!
5) Measure milli amp signal in series with positive input to the analog board. Write this number
down.
!
6) Subtract 4 mA from this reading. Write this number down.
!
7) Use the Model 310 Calibration chart to select the correct pipe size for the programming installed
on the Model 310. Go to the Max GPM @ 20 mA column, and record that number.
!
8) Divide the maximum GPM by 16 and write down that number.
!
9) Multiply that number (GPM per mA) by the adjusted mA reading from step 5.
!
10) Enter this number in MaxOut (:102).
For Example: You have a pump station with an 8 inch flow meter spool. Therefore, the maximum
GPM @ 20 mA is 3000 GPM. Start at step 5. Your mA reading is 14 ma. Subtracting 4 mA from
this reading gives you an adjusted reading of 10 mA for step 6. The max GPM @ 20 mA is 3000
GPM for step 7. Dividing this value by 16 yields 187.5 GPM per mA for step 8. Multiply the
adjusted reading of 10 mA from step 6 by 187.5. Your answer is 1875 GPM. Enter this value in
MaxOut (:102).
!
·
Tap the value next to any of these registers to open the calculator/keypad. Enter or edit the value.
(See also, Calculator/Keypad.)
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the previous screen.