Owner's manual
© 2013 Flowtronex
96
Omron Touch-Screen Display
!
!
!
!
!
!
!
1) With no flow, record the counts in raw data (:22) and enter that value in Min Raw (:62) and MinIn
(:72).
!
2) Remove the Model 310 input wires at the PLC, and connect your signal generator.
!
3) Generate a 20 mA signal.
!
4) Record the counts in raw data (:22) and enter that value in MaxIn (:82).
!
5) Disconnect the signal generator and reconnect the Model 310 wiring.
!
6) Enter 0 in MinOut(:92).
!
7) Use the Model 310 Calibration chart to select the correct pipe size.
!
8) Go to the Max GPM @ 20 mA column, and record that number in MaxOut (:102).
!
·
Tap the value next to any of these registers to open the calculator/keypad. Enter or edit the value.
(See also, Calculator/Keypad.)
!
·
Optionally, press the Main Menu touch key to return to the Main Menu. (See also, Main Menu.)
!
·
Optionally, press Back to return to the previous screen.
!
·
Optionally, press the down arrow
(
▼
)
to advance the next Calibration screen.
!
·
See also, Calibration Procedure without a Signal Generator.
!
2.13.5.3 Calibration Procedure without a Signal Generator
!
The calibration procedure without a signal generator is much more difficult and less accurate than the
procedure with a signal generator. It also requires you to use a calculator. Enter the information on
Calibration screen page 3,