Owner manual
AQUAFORCE Installation, Operation, and Maintenance
52
Appendix
7.2 AquaForce MODBUS Communication Points
Function Points # Point Range/ Modbus Units
Code Description Value Address
02 1 Pump #1 VFD Failure 1 = Failure 0 = O.K. 10001
02 2 Pump #1 Off Alarm 1 = Alarm 0 = O.K. 10002
02 3 Pump #2 VFD Failure 1 = Failure 0 = O.K. 10003
02 4 Pump #2 Off Alarm 1 = Alarm 0 = O.K. 10004
02 5 Pump #3 VFD Failure 1 = Failure 0 = O.K. 10005
02 6 Pump #3 Off Alarm 1 = Alarm 0 = O.K. 10006
02 7 Pump #4 VFD Failure 1 = Failure 0 = O.K. 10007
02 8 Pump #4 Off Alarm 1 = Alarm 0 = O.K. 10008
02 9 System Reset Required 1 = Yes 0 = No 10009
02 10 Pump #1 Enabled 1 = Enabled 0 = Disabled 10010
02 11 Pump #2 Enabled 1 = Enabled 0 = Disabled 10011
02 12 Pump #3 Enabled 1 = Enabled 0 = Disabled 10012
02 13 Pump #4 Enabled 1 = Enabled 0 = Disabled 10013
02 14 Pump #1 On/Off 1 = On 0 = Off 10014
02 15 Pump #2 On/Off 1 = On 0 = Off 10015
02 16 Pump #3 On/Off 1 = On 0 = Off 10016
02 17 Pump #4 On/Off 1 = On 0 = Off 10017
02 18 System Start/Stop 1 = Start 0 = Stop 10018
02 19 Analog Input #1 Failure 1 = Failure 0 = O.K. 10019
02 20 Analog Input #2 Failure 1 = Failure 0 = O.K. 10020
02 21 General Alarm 1 = Alarm 0 = O.K. 10021
02 22 System Operation Mode 1 = Auto 0 = Manual 10022
05 1 Pump Sequence Alternation 1 = Yes 0 = No 00001
05 2 System Reset Request 1 = Yes 0 = No 00002
05 3 System Start / Stop 1 = Start 0 = Stop 00003
04 1 Discharge Pressure 0 to Span (in AquaForce 30001 PSI
User Setup Menu)
04 2 Suction Pressure 0 to Span (in AquaForce 30002 PSI
User Setup Menu)
04, 06 3 AI #1 0 to Span (in AquaForce 30003,
User Setup Menu) 40003
04, 06 4 AI #2 0 to Span (in AquaForce 30004,
User Setup Menu) 40004
04, 06 5 Setpoint #1 0 to Span (in AquaForce 30005,
User Setup Menu) 40005
04 6 System Power (KW) 0 to Span (in AquaForce 30006 KW
User Setup Menu)
04 7 Drive #1 Current 0 to Span (in AquaForce 30007 A
User Setup Menu)
04 8 Drive #2 Current 0 to Span (in AquaForce 30008 A
User Setup Menu)
04 9 Drive #3 Current 0 to Span (in AquaForce 30009 A
User Setup Menu)