Owner manual
AQUAFORCE Installation, Operation, and Maintenance
37
Operation
5.4 Hand Manual Operation
1. If system is running press the START/STOP key to stop the system. The solid green LED for start/stop
will turn off and any running pumps will stop.
2. Press the AUTO/MANUAL key and the screen will display the following:
< >
Manual Speed: #%
STAT1 STAT2 STAT3
3. If the PUMP LED is not ashing green, enable a pump to run in manual by pressing the
PUMP 1 or PUMP 2 key.
4. Press the START/STOP key to run the enabled pump(s) in manual. After a brief time delay the
pump(s) starts, and the ashing green LED(s) for pump(s) will turn solid green.
5. Press the UP (▲) key to increase pump speed to a maximum of 100% of rated speed. Press the
DOWN (▼) key to decrease the speed to 0% where the pump will run at the minimum speed
congured in the VFD, typically 30 HZ.
6. Press the START/STOP key to stop the system. The running pump(s) will stop.
5.5 Setpoint Modication
To modify the setpoint, press the SETPT/2 key. The following SET POINT SELECTION screen will be
displayed:
Selection: # 0=Exit
1= Set Point
3= Control Set Point
Use the appropriate numeric key to select the desired menu, then press the ENTER key. A detailed description
of each menu follows. For example, to select the SET POINT menu, press the PV/1 key and then press the
ENTER key. The following menu will be displayed:
SP1= ##
Exit: $ (Y/N)
If you agree with the current setpoint settings press the YES/7 key followed by ENTER. If you would like
to modify the setpoint press the NO/0 key followed by ENTER at which point the setpoint in the upper left
portion of the screen will begin ashing.
Press the numeric key to modify the setpoint and press ENTER.
After modifying the set point, press the YES/7 key to accept the values and return to the SET POINT
SELECTION screen.
To select the CONTROL SET POINT menu, press the SETUP/3 key and then press the ENTER key. The
following menu will be displayed:
Control Selection: #
1= Set Point
3 = Com Ovrd Exit $(Y/N)
The displayed # value indicates the current active method for set point. To change the active control method,
press the NO/0 key and then press the ENTER key.
The Control Selection eld will start blinking. Change the current value by pressing desired numeric Keys and
then press ENTER key to conrm. Press the YES/7 key and ENTER key to accept the selection and return to
the SET POINT SELECTION screen.