Owner manual

AQUAFORCE Installation, Operation, and Maintenance
37
Operation
5.4 Hand Manual Operation
1. If system is running press the START/STOP key to stop the system. The solid green LED for start/stop
will turn off and any running pumps will stop.
2. Press the AUTO/MANUAL key and the screen will display the following:
< >
Manual Speed: #%
STAT1 STAT2 STAT3
3. If the PUMP LED is not ashing green, enable a pump to run in manual by pressing the
PUMP 1 or PUMP 2 key.
4. Press the START/STOP key to run the enabled pump(s) in manual. After a brief time delay the
pump(s) starts, and the ashing green LED(s) for pump(s) will turn solid green.
5. Press the UP () key to increase pump speed to a maximum of 100% of rated speed. Press the
DOWN () key to decrease the speed to 0% where the pump will run at the minimum speed
congured in the VFD, typically 30 HZ.
6. Press the START/STOP key to stop the system. The running pump(s) will stop.
5.5 Setpoint Modication
To modify the setpoint, press the SETPT/2 key. The following SET POINT SELECTION screen will be
displayed:
Selection: # 0=Exit
1= Set Point
3= Control Set Point
Use the appropriate numeric key to select the desired menu, then press the ENTER key. A detailed description
of each menu follows. For example, to select the SET POINT menu, press the PV/1 key and then press the
ENTER key. The following menu will be displayed:
SP1= ##
Exit: $ (Y/N)
If you agree with the current setpoint settings press the YES/7 key followed by ENTER. If you would like
to modify the setpoint press the NO/0 key followed by ENTER at which point the setpoint in the upper left
portion of the screen will begin ashing.
Press the numeric key to modify the setpoint and press ENTER.
After modifying the set point, press the YES/7 key to accept the values and return to the SET POINT
SELECTION screen.
To select the CONTROL SET POINT menu, press the SETUP/3 key and then press the ENTER key. The
following menu will be displayed:
Control Selection: #
1= Set Point
3 = Com Ovrd Exit $(Y/N)
The displayed # value indicates the current active method for set point. To change the active control method,
press the NO/0 key and then press the ENTER key.
The Control Selection eld will start blinking. Change the current value by pressing desired numeric Keys and
then press ENTER key to conrm. Press the YES/7 key and ENTER key to accept the selection and return to
the SET POINT SELECTION screen.