Owner manual

AQUAFORCE Installation, Operation, and Maintenance
29
Installation
4.10.25 Analog input test
Paths: Status Screens / Set up(3) / Test(5) / AI(3)
The Analog Input Test screen is displayed below:
Analog Inputs
1=###%
2=###%
The signal received on the corresponding analog input channel will be indicated in percent next to each input.
4mA = 0%, and 20mA = 100%. Analog inputs 1-2 are 4-20mA inputs. Press CLEAR key to exit the test.
4.10.26 Analog output test
Paths: Status Screens / Set up(3) / Test(5) / AO(4)
The Analog Output Test screen is displayed below:
Analog Output Test
AO1=###%
OK: $(Y/N)
The signal sent through the corresponding analog output channel will be indicated in percent next to each output.
4mA = 0%, and 20mA = 100%. Analog output is 4-20mA output. Press CLEAR key to exit the test.
4.10.27 LED test
Paths: Status Screens / Set up(3) / Test(5) / LED(5)
The LED test screen is displayed below:
LED Test
*** SOLID ***
*** OFF ***
*** FLASHING ***
All of the LED’s on the keypad will turn on, off, and then ash. The current status will be displayed on the
screen. The LED test is self terminating.
4.10.28 Key test
Paths: Status Screens / Set up(3) / Test(5) / Key(6)
The KEY test screen is displayed below:
Key Test
Press a key to test
Press clear to exit
Press any key except for the CLEAR key, and the display will conrm that the key is working by displaying the
key name. Press CLEAR key to exit.
4.10.29 Display test
Paths: Status Screens / Set up(3) / Test(5) / Display(7)
The DISPLAY test screen is shown below:
Press Clear To Exit
< 1 2 3 4 5 6 7 8 9
< 1 2 3 4 5 6 7 8 9
< 1 2 3 4 5 6 7 8 9
The display will show all black characters. Press CLEAR key to exit the test.