Installation
STAGE/DESTAGE SETUP MENU ITEMS (continued)
Menu Item Variable Default Range Field
Value
PV Destage Destage: ###% 85 0-100
Enter the percentage of the stabilized speed at which
the lag pump will stop, %.
Destg Pr Timer: ### s 30 0-999
Proof timer prior to stopping lag pump, seconds.
HD Spd: ### % 50 0-100
The lowest speed at which parallel pumps will operate
prior to destaging the lag pump, %. It must be
greater or equal to minimum frequency.
HD Pr Tm: ### s 30 0-999
The proof timer prior to destaging the lag pump when
operating below the HD speed, seconds.
Power Limit Enable Power Stage N Y/N
Stage Limit $ (Y/N)
Exit: $(Y/N)
Reads motor current entered in pump set up to stage
on next pump after a xed time delay should current
limit be reached.
4.10.4 VFD menu
Paths: Status Screens / Set up(3) / System(4) / VFD(2)
The rst screen has been displayed below:
<Selection:# >
1 = VFD Setup
2 = VFD Set Parameter
3 = VFD Read Parameter
Press the NEXT ( ) key to go to the next screen.
The display now shows:
<Selection: # >
4 = All DIS SEN Fail
▲