Datasheet
ACM06 Series
www.xppower.com
2
AC-DC Power Supplies
General
Characteristic Minimum Typical Maximum Units Notes & Conditions
Efficiency 80 %
Typical average of efficiencies measured at 25%,
50%, 75% and 100% load and 115 VAC input
Energy Efficiency Level VI
Isolation 4000 VAC Input to Output, 2 x MOPP
Leakage Current 20 100
µA
At 264 VAC, 60 Hz, from output to ground
Switching Frequency 24 70
kHz
Variable
Mean Time Between Failure 250 kHrs MIL-HDBK-217F at 25 °C GB
Weight 0.22 (100) lb (g) Body only
Environmental
Characteristic Minimum Typical Maximum Units Notes & Conditions
Operating Temperature 0 +60 °C
Derate from 100% load at 40 °C to 50% load
at 60 °C
Storage Temperature -20 +85 °C
Operating Humidity 5 90 % RH, non-condensing
Operating Altitude 5000 m
Cooling Natural convection
Shock
1 m drop onto concrete on each of 6 axes, non
operating
Vibration 10 300 Hz 2 g, 0.3 decades/min, 15 mins for each of 3 axes
EMC: Emissions
Phenomenon Standard Test Level Notes & Conditions
Conducted EN55032 Level B
Radiated EN55032 Level B
Harmonic Current EN61000-3-2 Class A
Voltage Flicker EN61000-3-3
EMC: Immunity
Phenomenon Standard Test Level Criteria Notes & Conditions
Medical Device EMC IEC60601-1-2 Ed.4.0 : 2014 as below
Low Voltage PSU EMC EN61204-3 High severity level as below
ESD Immunity EN61000-4-2 ±8 kV contact, ±15 kV air A
Radiated Immunity EN61000-4-3 10 V/m A
EFT/Burst EN61000-4-4 Level 3 A
Surge EN61000-4-5 Level 2 A
Conducted Immunity EN61000-4-6 6 V A
Magnetic Fields EN61000-4-8 30 A/m A
Dips and Interruptions
EN61000-4-11
Dip: 100% 10 ms A
Dip: 70% 500 ms B
Int: 100% 5000 ms B
EN60601-1-2
Dip: 30% 25 AC Cycles A
Int: 100% 0.5 AC Cycle At 8 angles, A at 115 VAC, B at 100 VAC
Int: 100% 1 AC Cycle B
Int.: >95% 5000 ms B