8.- OPERATION INTERFACE
UPS FRONT PANEL: PUSH BUTTON
RACK FRONT PANEL TOWER FRONT PANEL
Both Rack and Tower type UPS offer same 4 function buttons as described below:
ON / ENTER POWER ON : Keep selected during 1 second to power UPS ON.
ENTER : It Works as “ENTER” or confirmation function when LCD is in configuration menu mode.
OFF / ESCAPE POWER OFF : Keep selected to turn UPS OFF.
ESCAPE : It Works as ESCAPE key when LCD is in configuration menu mode.
TEST / UP BATTERY TEST : By selecting TEST key UPS enters into battery test mode during 10s.
UP : It Works as UP key when LCD is in configuration menu mode.
MUTE / DOWN ALARM MUTE : It mutes alarm beep in progress.
DOWN : It Works as DOWN key when LCD is in configuration menu mode,
TEST / UP + MUTE / DOWN - Simultaneous Activation
CONFIGURATION MODE : When these 2 keys are activated at same time during 1s
UPS FRONT PANEL: LED INDICATOR LIGHTS
There are 4 LED indication lights in front panel, located below LCD. These 4 LEDs describe UPS condition as follow:
MODE
Bypass Line Battery Fault
UPS is in Auto-check mode during start-up.
● ● ● ●
BYPASS Mode
● ○ ○ ○
NORMAL Mode
○ ● ○ ○
BATTERY Mode
○ ○ ● ○
BATTERY TEST in progress
● ● ● ○
ECO Mode Activated
● ● ○ ○
UPS in Failure
○ ○ ○ ●
● LED = ON / ○LED = OFF