12. APPENDIX C - APPLICATION NOTES
12.1. HALO CONTROLLER HOOK UP WITH ANN-6L
RECEIVE
ANTENNA
RBC
FCC ID# HE7MAX
TRANSMIT OUTPUT
SEA #1
SEA #2
Made in Canada . . with care
Controller
by
Power
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
+24V DC Input
System Ground
+12V Ou 200 ma
System Ground
Weigand 0/Data
Weigand 1/Gnd
System Ground
MagOut 24V 200 ma
Door Switch In
System Ground
Unlock In
Override In
Strobe In
N.O
COM
N.C.
N.O
COM
N.C
Relay #1 Relay #2
Alarm In
OFF ON
R2 Controller
Magnetic Contacts located at door
and door frame are closed when door is closed.
(Supplied with HALO Controller Pak)
Magnetic Door Lock,
24 VDC 160 mA Max
ANN-6L
(Front view)
SW2
J2
J1
SW1
P1
P3
P2
24V
12V
OPEN
OFFON
Internal
Beeper
Voltage
Select
C1 = Commons Grounded
Return Inputs high
C2 = Commons Positive
Return Inputs low
1 2 3
1A
1B
2A
2B
3A
3B
Commons
Power Ground
Common
4B
5A
5B
6A
6B
4A
12/24 VDC
Reset
Beeper
Ground
N.O
N.C.
Common
Relay
Form C SPDT
1A Max @ 24 VDC
82Ω, 2W
External Speaker
(150 mA Max)
SW1 Settings
Sel #1: Open - Alarm Input High active
Closed - Alarm Input Low active
Sel #2: Open - Audible alarm on latched input (A) only
Closed - Audible alarm on both latched and non-latched
Sel #3: Open - Relay activated on latched input (A) only
Closed - Relay activated according to Sel #2 setting
Output low when
Reset button
pressed
24 VDC outboard
relay, 20 mA max
Alarm Inputs 1 to 6 (active when grounded)
A=Latching, Flashing Red light and audible alarm
B=Non-Latching, Flashing Yellow light, no audible alarm
ANN-6L
(Rear view)
Functional Description
Because the door switch function is utilized (Pin 9 of Controller), the door
will be locked by the Controller if it is sensed to be closed when a
transponder enters the field. Data is sent to the HALO Computer, but
Relays #1 and #2 are not activated (Pins 15 to 20). The outboard relay
is energized and input 1B of ANN-6L is grounded so that the ANN-6L
displays a flashing yellow light (1B is a non-latched input).
However, if the door is sensed to be open when a Transponder enters the
field, the alarm will be instant and alarm data will be sent to the Computer,
and both Relays #1 and #2 will be activated for the duration set within
the Controller. Input 1A of the ANN-6L is grounded through Relay #1 of
the Controller, resulting in a flashing red light and audible alarm (if enabled).
As input 1A is a latching input, the ANN-6L requires to be Reset for the
alarm condition to be silenced.
Low Input forces
ANN-6L to Reset