User's Manual
Installation Guide: Proximity Tag Reader Installation Guide: Proximity Tag Reader
Specifications
General
Input Frequency . . . . . . . . . . . . . . . . . . . .434 MHz
Output Frequency . . . . . . . . . . . . . . . . . .307 kHz
Input Voltage . . . . . . . . . . . . . . . . . . . . . . .12 VDC at 300 mA
Detection Zone . . . . . . . . . . . . . . . . . . . . .1 ft. to 5 ft. (0.30 m to 1.5 m)
Additional Inputs/Outputs . . . . . . . . . .Dry Contact Input
Options
Operating Modes . . . . . . . . . . . . . . . . . . .Features 6 operating modes
Adjustable LF Field. . . . . . . . . . . . . . . . . .Allows adjustment of Tag Detection Zone to suit
application
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Input can be configured for EOL (security), and
normally open or normally closed switches
Addressable . . . . . . . . . . . . . . . . . . . . . . . .Addressable from 0 to 255
Network
LF Link. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Uses LF link to connect to security network.
Network wires NOT required.
Physical
Operating Temperature . . . . . . . . . . . . .32° F to 131° F (0° C to 55° C)
Storage Temperature . . . . . . . . . . . . . . .-22° F to 140° F (-30° C to 60° C)
Relative Humidity . . . . . . . . . . . . . . . . . . .90% non-condensing
Size
Power Supply . . . . . . . . . . . . . . . . . . . . . . .12 VDC regulated
Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . .surface mount
Page 13 981-000300-000 R1.00 (Draft)
11 Turn off Test Mode by one of two methods:
Remove power.
Set the PTR to its usual operating mode. It is not necessary to remove
power to change operating modes. See Table 1 on page 8 for a list of
End of Procedure
operating modes and switch settings.
Setting the Address
Each PTR must have an address unique within its floor or facility. Addresses are entered
in binary format using the Address Dip Switch. The PTR can accept addresses ranging
from 0 to 255.
The least significant bit of the binary address is on the right hand side of the Address
DIP Switch. Figure 5 shows the binary value of every switch in the Address DIP Switch.
Table 5, appended to this guide, shows all address values and switch positions.
Figure 5: Address Dip Switch Showing Switch’s Binary Values
Selecting an Operating Mode
Operating modes are selected using the Mode Switches on the Options DIP Switch.
The location of the Options DIP Switch is shown Figure 2 on page 4.
Page 6 981-000300-000 R1.00 (Draft)
ADDRESS
ON
1 2 3 4 5 6 7 8
2
4
= 16
2
5
= 32
2
6
= 64
2
7
= 128
Least Significant Bit
A B C D E F G H
2
0
= 1
2
1
= 2
2
2
= 4
2
3
= 8