Temperature Control Programming Procedure
OVEN SERVICE PROCEDURES
Ser1 OFF
P1 5˚C/22˚F
P3 0
P4 315˚C/600˚F
P5 reU
P6 4-20
P9 AL1.P
P10 H.A.
P11 nonE
P16 0
P17 SFtA
P18 norL
P19 norL
P24 reU
P25
OFF
P28 0
P29 0n
P30 0
P34 OFF
P36 tn.30
P37 0
P39 n0FL
P41 P.I.d.
P42 10.0
P43 Fn.SP
P44 0
SP 260°C/500°F
SP2 0
nnn 3111/OFF
AL1 315°C/600°F
HSA1 0.1
Pb 5.0
t
i
5.00
td 0.00
1P 30.0
rL 204°C/400°F
rH 310˚C/590°F
Grd1 InF
Grd2 InF
OLH 100.00
toL InF
rnP InF
Fi
g
ure 4
Fi
g
ure 2
Fi
g
ure 3
Read the entire instruction before programming.
TIP
Configuration Button Functions
<FUNC> =The new setting of the selected parameter is stored and the
display advances to the next parameter. This is required be
tween each parameter.
UP= Increases the setting of the selected parameter.
DOWN=Decrease the setting of the selected parameter.
1. Open V101 switch for Basic/Advanced Configuration (Figure 1)
Remove instrument from its case
Open switch V101
Verify that jumper J106, is configured as shown
Re-insert the instrument back in its case
2. Basic Configurations
Using the configuration buttons, scroll through parameter codes,
changing them to match (Figure 2)
After P17 _._._._. Will appear
Using the configuration buttons scroll to 262 and press <FUNC>
to enter Advanced Configurations
3. Advanced Configuration Procedure
Using the configuration buttons scroll through parameter codes
changing them to match (Figure 3)
4. Close V101 switch after Basic/Advanced Configuration (Figure 1)
Remove instrument from its case
Close Switch V101
Re-insert the instrument back in its case
5. Operating Parameters Procedure (Figure 4)
On the first pass through change nnn to 3111 to unlock the ad
vanced configuration
Scroll through the parameter codes again and change the nnn to
5 this locks the advanced configuration
Scroll through the parameter codes again and verify nnn in ON