8 channels numbered 64 to 71 utilize LoRa 500 kHz BW starting at 903.0 MHz and incrementing
linearly by 1.6 MHz to 914.2.
For AU915:
64 channels numbered 0 to 63 utilize LoRa 125 kHz BW starting at 915.2 MHz and incrementing
linearly by 0.2 MHz to 927.8.
8 channels numbered 64 to 71 utilize LoRa 500 kHz BW starting at 915.9 MHz and incrementing
linearly by 1.6 MHz to 927.1.
For CN470:
80 channels numbered 0 to 79 utilize LoRa 125 kHz BW starting at 470.3 MHz and incrementing
linearly by 0.2 MHz to 486.1.
16 channels numbered 80 to 95 utilize LoRa 125 kHz BW starting at 486.3 MHz and incrementing
linearly by 1.6 MHz to 489.3.
7.2 Device Settings
7.2.1 General
Location:
Ursalink ToolBox (PC): Device Settings General
Ursalink ToolBox (APP): Device Settings General Settings
Device General Settings
Item Description Default
Device Type Show the type of the device. Null
Reporting
Interval
The sensor reports the sampling data at regular
intervals.
Range: 5-30 (mins)
10
Screen Smart
Mode
Screen display stops updating data for power saving.
When Activity Level (PIR) = 0 and lasts for 20 minutes,
screen will go to sleep mode until detected Activity Le
vel (PIR) > 0.
Enabled
Temperature
Unit
Configure the unit of temperature shown on the
screen and status page.
Note: Threshold settings should be changed after
changing unit.
Change
Password
Change the password used for changing device status
and writing configuration.
Disabled
7.2.1 Data Collection
Select the items you need to collect or not to collect.
Location:
Ursalink ToolBox (PC): Device Settings Data Collection Settings