User's Guide

20
3. Disable the e-ink screen display.
4. Set CO
2
bad threshold as 1500ppm and polluted threshold as 1000 ppm.
Appendix
Carbon Dioxide Levels and Guidelines
CO
2
Level Description
400 ppm Normal outdoor air level.
400-1000 ppm Typical level indoors with good ventilation.
1000-2000 ppm Poor air quality - requires ventilation.
2000 ppm
Headaches, sleepiness and stagnant, stale, stuffy air.
Poor concentration, loss of attention, increased heart rate
and slight nausea may also be present.
5000 ppm
Workplace exposure limit (as 8-hour TWA) in most
jurisdictions.
> 40000 ppm
Exposure may lead to serious oxygen deprivation resulting
in permanent brain damage, coma, even death.
-END-
ff2d00
Channel Type Value
ff 2d (Screen Display)
00: Disable the display
ff5401dc05e803
Channel Type Value
ff
54 (Set CO
2
Threshold)
Byte 1: 01 = enable
Byte 2-3: dc 05 => 05 dc = 1500 ppm (Bad threshold)
Byte 4-5: e8 03 => 03 e8 = 1000 ppm (Polluted threshold)