User's Manual

For safe use of electricity, please add circuit breaker protection in the input part
of charging pile. Connect the L1 lead to the grid L1, connect the L2 lead to the grid L2,
connect the PE lead to the grid PE (for all Version).
Circuit Breaker Options table
Output Amperage (A)
Circuit Breaker Options (A)
16A
20A
32A
40A
40A
50A
48A
60A
USER MANUAL USER MANUAL
1413
8.4 Tools and Materials Required
Tools required before installing the Wall-Mounted charger, gather the following tools:
• Wire stripper
• Crimpers for European terminals
• Phillips screwdriver for M5
• Slotted screwdriver for 4~5.5MM
• Adjustable Wrench M6
• Head gasket screw 10-10.5mm
• Voltmeter or digital multi-meter (for measuring AC voltage at the installation site)
• The inserting cable should meet the best waterproof performance. It is recommended to use
3 core / 7AWG cable (XLPE or equivalent cable) to pull the cable from the distribution box.
• Level ruler
• Pencil or marker
• Machine drill
Installation Instructions
“This device shall be mounted at a sufficient height from grade such that the height of the
storage means for the coupling device is located between 600mm (24 inches) and 1.2m (4
feet) from grade.”