Specifications
High DC current reslstance meter
Micro OhmMeter
P.36
DV-POWER
TO place an order call (852) 2408 8880
Wardson Limited
Unit A & B, 21/F., Infotech Centre, No. 21 Hung To Road Kwun Tong, Kowloon, Hong Kong. Web: www.wardsonlimited.com
Tel: (852) 2408 8880 Fax: (852) 2408 9688 E-mail: info@wardsonlimited.com
High DC current reslstance meter
Micro OhmMeter
Using RMO100 with current clamp meter it is
possible to make safer measurement of breakers
with both sides of the breaker grounded.
Measuring the current through the ground
connection and reducing this value from the
total current is an additional safety feature.
The RMO Remote Control Unit is an optional
control unit that is used to start and stop the
tests from a remote location, away from the
actual RMO.
Provided that, for a series of tests, the same
test current is fed through the test object,
multiple measurements can be carried out
with the RMO Remote Control Unit.
Connecting a Test Object to RMO100 Remote Control Unit Connecting a Test Object to RMO100
Remote Control Unit Current clamp meter With
RMO100 turned off, connect RMO100 to the
test object (RX) in such a way that the measuring
cables from the "Voltage Sense" sockets are
attached as close as possible to RX, and in
between the current feeding cables. That way,
resistance of both cables and clamps is almost
completely excluded from the resistance
measurement.