B. Specifications
RS232 Port Interface: Seven (7) RS232 serial inputs use DB9
connectors configured as DTE ports
Internal Modem Interface: RJ11 connectors for connection to
your telco line
Coding: Asynchronous, 7/8 bits ASCII.
Parity: Even, Odd, None
Stop Bits: 1or2.
Data Rate: 300 to 115.2K bps (standard rates).
Flow Control: XON/XOFF, RTS/CTS, Both, or None.
Timeout: No activity timeout disconnects port. 1, 5, 10, 15, 30
seconds, 1, 5, 15, 30, 90 minutes.
Memory: Stores Parameters and captured data. Non-volatile
32K SRAM buffer memory per port.
Break: Accept Break or Refuse Break
SetUp Switches: 8 position, sets default parameters for baud
rate, flow control, response format, and command echo.
LEDs: On, Ready, Activity (for each RS232 Port).
Temperature: 0°Cto45°C (operating)
Power:
AC Version: IEC-32 Inlet, 115/230 VAC, 50/60 Hz, 5 watts
DC Version: Terminal Strip, -48 VDC, 0.2 Amp Max.
Size: 1.7" High x 17.15" Wide x 6.8" Deep (One Rack Unit)
Weight: 8 lbs. shipping weight
Humidity: 10 to 90% RH, Non-Condensing
Venting: Side vents are used to dissipate heat generated within
the unit. When mounting the unit in an equipment rack, make
certain to allow adequate clearance for venting.
Apx-2
APS-8M User’s Guide